![YASKAWA A1000 HHP Programming Manual Download Page 60](http://html1.mh-extra.com/html/yaskawa/a1000-hhp/a1000-hhp_programming-manual_3232370060.webp)
• When an analog input is set to “Auxiliary frequency 2” (H3-02, H2-06, or H2-10 = 3), the value set to this input will be used
as the Multi-Step Speed 3 instead of the value set to parameter d1-03. If no analog inputs are set for “Auxiliary frequency
2”, then d1-03 becomes the reference for Multi-Step Speed 3.
Select the different speed references as shown in
.
illustrates the multi-step speed selection.
Table 1.27 Multi-Step Speed Reference and Terminal Switch Combinations
Reference
Multi-Step
Speed
H1-
oo
= 3
Multi-Step
Speed 2
H1-
oo
= 4
Multi-Step
Speed 3
H1-
oo
= 5
Multi-Step
Speed 4
H1-
oo
= 32
Jog Reference
H1-
oo
= 6
Frequency Reference 1 (set in b1-01)
OFF
OFF
OFF
OFF
OFF
Frequency Reference 2
(d1-02 or input terminal A1, A2, A3)
ON
OFF
OFF
OFF
OFF
Frequency Reference 3
(d1-03 or input terminal A1, A2, A3)
OFF
ON
OFF
OFF
OFF
Frequency Reference 4 (d1-04)
ON
ON
OFF
OFF
OFF
Frequency Reference 5 (d1-05)
OFF
OFF
ON
OFF
OFF
Frequency Reference 6 (d1-06)
ON
OFF
ON
OFF
OFF
Frequency Reference 7 (d1-07)
OFF
ON
ON
OFF
OFF
Frequency Reference 8 (d1-08)
ON
ON
ON
OFF
OFF
Frequency Reference 9 (d1-09)
OFF
OFF
OFF
ON
OFF
Frequency Reference 10 (d1-10)
ON
OFF
OFF
ON
OFF
Frequency Reference 11 (d1-11)
OFF
ON
OFF
ON
OFF
Frequency Reference 12 (d1-12)
ON
ON
OFF
ON
OFF
Frequency Reference 13 (d1-13)
OFF
OFF
ON
ON
OFF
Frequency Reference 14 (d1-14)
ON
OFF
ON
ON
OFF
Frequency Reference 15 (d1-15)
OFF
ON
ON
ON
OFF
Frequency Reference 16 (d1-16)
ON
ON
ON
ON
OFF
Jog Frequency Reference (d1-17)
−
−
−
−
ON
<1> The Jog frequency overrides all other frequency references.