Digital Operator Display
Error Name
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for pulse train (H6-06).
Cause
Possible Solutions
Scaling for the pulse train monitor is set to 0 (H6-07 = 0) while H6-06 is not
set to 101, 102, 105, or 116.
Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105,
or 116.
Digital Operator Display
Error Name
oPE15
Torque Control Setting Error
Parameter settings that are not allowed in combination with Torque Control
have been set.
Cause
Possible Solutions
Torque Control is enabled (d5-01 = 1) while the Speed/Torque Control
switch function is assigned to a digital input (H1-
oo
= 71).
Correct the parameter settings.
Either d5-01 is set to 1 to enable Torque Control, or the Speed/Torque Control
switch is assigned to a digital input H1-
oo
= 71, while at the same time:
• Droop Control is enabled (b7-01 ≠ 0), or
• Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled
(L3-04 = 2 or 5), or
Digital Operator Display
Error Name
oPE16
Energy Savings Constants Error
Cause
Possible Solutions
In AOLV/PM, the automatically calculated energy saving coefficients are
out of the allowable range.
Check and correct the motor data in E5 parameters.
Digital Operator Display
Error Name
oPE18
Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.
Cause
Possible Solutions
One of the following errors occurred while online tuning was enabled in OLV
(A1-02 = 2):
• E2-02 was set below 30% of the original default value
• E2-06 was set below 50% of the original default value
• E2-03 = 0
Set E2-02, E2-03, and E2-06 to the correct values.