Table A.8 YEC 690 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
Constant
No.
Name
Unit
Default Settings
Note: 690 V class default values when o2-o9 = 0
–
Model Type
6300
6600
6900
6C00
6F00
C6-01
ND/HD Select
–
HD
ND
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
–
241
(F1H)
241
(F1H)
242
(F2H)
242
(F2H)
243
(F3H)
243
(F3H)
244
(F4H)
244
(F4H)
245
(F5H)
245
(F5H)
Inverter Rated Current
A
360.0
414.0
700.0
800.0
1050.0
1200.0
1400.0
1600.0
1750.0
2000.0
E2-11
(E4-11)
Motor Rated Power
KW
300.0
335.0
600.0
670.0
900.0
1005.0
1200.0
1340.0
1500.0
1675.0
b3-04
V/f Gain during Speed Search
%
80
80
80
80
80
80
80
80
80
80
b3-06
Output Current 1 during
Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
E2-01
(E4-01)
Motor Rated Current
A
350.0
350.0
700.0
700.0
1050.0
1050.0
1400.0
1400.0
1750.0
1750.0
E2-02
(E4-02)
Motor Rated Slip
Hz
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
E2-03
(E4-03)
Motor No-Load Current
A
70.0
70.0
140.0
140.0
210.0
210.0
280.0
280.0
350.0
350.0
E2-05
(E4-05)
Motor Line-to-Line
Resistance
mΩ
14.000
14.000
10.000
10.000
8.000
8.000
7.000
7.000
6.000
6.000
E2-06
(E4-06)
Motor Leakage Inductance
%
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W
0
0
0
0
0
0
0
0
0
0
L2-02
Momentary Power Loss Ride-
Through Time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Momentary Power Loss
Minimum Baseblk Time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-04
Momentary Power Loss
Voltage Recovery Time
s
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
130
130
130
130
L8-38
Carrier Frequency Reduction
Selection
–
2
2
2
2
2
2
2
2
2
2
A.18 Defaults by Drive Model and Duty Rating ND/HD
312
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Summary of Contents for A1000 HHP
Page 359: ......