No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
V/f w/PG (1)
OLV (2)
CLV (3)
L8-40
Carrier Frequency Reduction Off Delay
Time
0.00 to 2.00
0.01 s
0.50
0.50
0.50
0.50
o1-03
Digital Operator Display Selection
0 to 3
1
0
0
0
0
o1-04
V/f Pattern Display Unit
0 to 1
1
—
—
—
0
<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
<2> This setting value depends on a Maximum Applicable Motor Capacity in models CIMR-A
5A0099 to 5A0242: 2.00 in Open Loop Vector Control, 0.05 in Closed Loop Vector Control.
<3> This setting value depends on a Maximum Applicable Motor Capacity: 1000 s in models CIMR-A
<4> Default setting is dependent on parameter C6-01, Drive Duty Selection.
<5> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 40.0%) instead of in Hz.
<6> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
<7> This setting value depends on a Maximum Applicable Motor Capacity and V/f pattern selection in parameter E1-03.
<8> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (-100.0 to 100.0%) instead of in Hz.
u
E3-01 (Motor 2 Control Mode) Dependent Parameters
Table A.3 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (E3-01)
V/f (0)
V/f w/PG (1)
OLV (2)
CLV (3)
C3-21
Motor 2 Slip Compensation Gain
0.0 to 2.5
0.1
0.0
–
1.0
1.0
C3-22
Motor 2 Slip Compensation Primary Delay
Time
0 to 10000
1 ms
2000
–
200
–
C5-21
Motor 2 ASR Proportional Gain 1
0.00 to 300.00
0.01
–
0.20
–
20.00
C5-22
Motor 2 ASR Integral Time 1
0.000 to 10.000
0.001 s
–
0.200
–
0.500
C5-23
Motor 2 Proportional Gain 2
0.00 to 300.00
0.01
–
0.02
–
20.00
C5-24
Motor 2 ASR Integral Time 2
0.000 to 10.000
0.001 s
–
0.050
–
0.500
C5-26
Motor 2 Carrier Frequency Selection
1 to F
–
7
E3-04
Motor 2 Maximum Output Frequency
40.0 to 150.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-05
Motor 2 Maximum Output Voltage
0.0 to 510.0
0.2 V
400.0
400.0
400.0
400.0
E3-06
Motor 2 Base Frequency
0.0 to 150.0
0.1 Hz
60.0
60.0
60.0
60.0
E3-07
Motor 2 Mid Output Frequency
0.0 to 150.0
0.1 Hz
3.0
3.0
3.0
0.0
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 510.0
0.2 V
30.0
30.0
22.0
0.0
E3-09
Motor 2 Minimum Output Frequency
0.0 to 150.0
0.1 Hz
1.5
1.5
0.5
0.0
E3-10
Motor 2 Minimum Output Voltage
0.0 to 510.0
0.2 V
18.0
18.0
4.0
0.0
<1> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<2> Values shown here are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690
A.16 Control Mode Dependent Parameter Default Values
308
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual