Register No.
Contents
00E5H
oFC3x Contents (CN5-C)
bit 0
Comm. ID Error (oFC30)
bit 1
Model Code Error (oFC31)
bit 2
Sumcheck Error (oFC32)
bit 3
Comm. option timeout waiting for response (oFC33)
bit 4
MEMOBUS Timeout (oFC34)
bit 5
Drive timeout waiting for response (oFC35)
bit 6
CI Check Error (oFC36)
bit 7
Drive timeout waiting for response (oFC37)
bit 8
Control Command Selection Error (oFC38)
bit 9
Drive timeout waiting for response (oFC39)
bit A
Control Response Selection 1 Error (oFC40)
bit B
Drive timeout waiting for response (oFC41)
bit C
Control Response Selection 2 Error (oFC42)
bit D
Control Response Selection Error (oFC43)
bit E, F
Reserved
00E6H to 00FFH
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04, E4-04, or E5-05 depending on the motor being used.
<5> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
u
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Contents
0001H
Digital Input Command
bit 0
Forward Run (0: Stop 1: Run)
bit 1
Direction Command (0: Forward, 1: Reverse)
bit 2, 3
Reserved
bit 4
External Fault
bit 5
Fault Reset
bit 6 to B
Reserved
bit C
Multi-Function Digital Input S5
bit D
Multi-Function Digital Input S6
bit E
Multi-Function Digital Input S7
bit F
Multi-Function Digital Input S8
0002H
Frequency Reference
30000/100%
B.9 MEMOBUS/Modbus Data Table
340