Setting 2: Conveyor Application
Table 1.7 Conveyor: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Duty Rating
0: Heavy Duty
L3-04
Stall Prevention Selection during Deceleration
1: Enabled
Table 1.8 Conveyor: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
A1-02
Control Method Selection
C1-02
Deceleration Time 1
b1-01
Frequency Reference Selection
E2-01
Motor Rated Current
b1-02
Run Command Selection
L3-04
Stall Prevention Selection during Deceleration
C1-01
Acceleration Time 1
−
−
Setting 3: Exhaust Fan Application
Table 1.9 Exhaust Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C6-01
Duty Selection
1: Normal Duty
E1-03
V/f Pattern Selection
0FH
E1-07
Mid Output Frequency
30.0 Hz
E1-08
Mid Output Frequency Voltage
50.0 V
L2-01
Momentary Power Loss Operation Selection
1: Enabled
L3-04
Stall Prevention Selection during Deceleration
1: Enabled
Table 1.10 Exhaust Fan: User Parameters (A2-01 to A2-16)
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection
E1-07
Mid Output Frequency
b1-02
Run Command Selection
E1-08
Mid Output Frequency Voltage
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
b3-01
Speed Search Selection at Start
H1-05
Multi-Function Digital Input Terminal S5 Function
Selection
C1-01
Acceleration Time 1
H1-06
Multi-Function Digital Input Terminal S6 Function
Selection
C1-02
Deceleration Time 1
H1-07
Multi-Function Digital Input Terminal S7 Function
Selection
E1-03
V/f Pattern Selection
L5-01
Number of Auto Restart Attempts
Setting 4: HVAC Fan Application
Table 1.11 HVAC Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
b1-17
Run Command at Power Up
1: Run command issued, motor operation start
C6-01
Duty Rating
1: Normal Duty
C6-02
Carrier Frequency Selection
1: 2.0 kHz
H2-03
Terminals P2 Function Selection
39: Watt Hour Pulse Output
1.1 A: Initialization
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
15
1
Parameter Details