A.12 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u
o1: Digital Operator Display Selection
No.
(Addr.
Hex)
Name
Description
Values
Page
o1-01
(500)
Drive Mode Unit Monitor
Selection
All Modes
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: U
o
-
oo
.
Default: 106
(Monitor U1-06)
Range: 104 to 809
o1-02
(501)
User Monitor Selection after
Power Up
All Modes
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Range: 1 to 5
o1-03
(502)
Digital Operator Display
Selection
All Modes
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
Default:
Range: 0 to 3
o1-04
(503)
V/f Pattern Display Unit
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
CLV/PM
CLV
0: Hz
1: r/min
Default:
Range: 0, 1
o1-10
(520)
User-Set Display Units
Maximum Value
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Default:
Range: 1 to 60000
o1-11
(521)
User-Set Display Units
Decimal Display
Default:
Range: 0 to 3
<1> Default setting is dependent on parameter A1-02, Control Method Selection.
<2> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.
u
o2: Digital Operator Keypad Functions
No.
(Addr.
Hex)
Name
Description
Values
Page
o2-01
(505)
LO/RE Key Function
Selection
All Modes
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Range: 0, 1
o2-02
(506)
STOP Key Function
Selection
All Modes
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Range: 0, 1
o2-03
(507)
User Parameter Default
Value
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Default: 0
Range: 0 to 2
o2-04
(508)
Drive Model Selection
All Modes
Enter the drive model. Setting required only if installing a new control board.
Default:
Determined by
drive capacity
A.12 o: Operator-Related Settings
292