H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
Description
Page
13
Reverse Jog
All Modes
Closed: Runs reverse at the Jog frequency d1-17.
14
Fault reset
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
15
Fast Stop (N.O.)
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
16
Motor 2 selection
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
CLV
Open: Motor 1 (E1-
oo
, E2-
oo
)
Closed: Motor 2 (E3-
oo
, E4-
oo
)
17
Fast Stop (N.C.)
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
18
Timer function input
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the
timer function output (H2-
oo
= 12).
19
PID disable
All Modes
Open: PID control enabled
Closed: PID control disabled
1A
Accel/decel time selection 2
All Modes
Used in conjunction with an input terminal set for “Accel/decel time selection 1”
(H1-
oo
= 7), and allows the drive to switch between accel/decel times 3 and 4.
1B
Program lockout
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to
the digital operator).
Closed: Parameters can be edited and saved.
1E
Reference sample hold
All Modes
Closed: Samples the analog frequency reference and operates the drive at that speed.
20 to 2F External fault
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
30
PID integral reset
All Modes
Closed: Resets the PID control integral value.
31
PID integral hold
All Modes
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
32
Multi-Step Speed
Reference 4
All Modes
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use
parameters d1-09 to d1-16 to set reference values.
34
PID soft starter cancel
All Modes
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
A.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
271
A
Parameter List