Installation and Setup
WebRelay-10 Users Manual
-
latch relay when input 1 changes (reset via web)
: Each time the input is tied to ground or
when the input is open, the relay turns
ON
. Once the relay is on, it will stay
ON
(unaffected
by input change) until it is turned
OFF
via the web (or command) by a user or WebRelay-10
Plus™ is powered off. This option is useful for alarming functions.
-
toggle relay when input 1 on
: When the input is tied to ground, the relay will change
states. When the input is open, the relay will remain in its current state.
-
toggle relay when input 1 off
: When the input is open, the relay will change states. When
the input is tied to ground, the relay will remain in its current state.
-
toggle relay when input 1 changes
: Each time the input is tied to ground or open, the
relay will change states.
-
pulse relay when input 1 on
: When the input is tied to ground, the relay will pulse for the
Pulse Duration specified. The input may stay tied to ground and the pulse time will not be
affected. If the input is tied to ground, opened, and then tied to ground again, before the end
of the pulse time, the Pulse Duration timer will be restarted (it will re-start each time the input
is tied to ground) and the relay will continue to remain
ON
until the timer expires.
-
pulse relay when input 1 off
: When the input is open, the relay will pulse for the Pulse
Duration specified. The input can remain open and the pulse time will not be affected. If the
input is tied to ground and re-opened before the end of the pulse time, the Pulse Duration
timer will be re-started (it will re-start each time the input is open) and the relay will continue
to remain
ON
until the timer expires.
-
pulse relay when input 1 changes
: Each time the input is tied to ground or opened, the
relay will pulse for the Pulse Duration specified. If the state of the input changes before the
end of the pulse, the timer will be re-started (it will re-start each time the input changes) and
the relay will continue to remain
ON
until the timer expires.
Control Input (WebRelay-10 Plus™ only)
Selects which input will control the relay
-
Input 1
or
Input 2
Email Option
Simple email messages can be sent when relays are turned
ON
or
OFF
. This parameter is used to
specify what conditions, if any, will cause email messages to be sent. Note that email notification will
work only if the email settings are correctly set up in the
Network
setup page. The following options
are available:
-
No Email Messages
: No email notifications will be sent when relay changes.
-
Send Email when relay on
: Email notifications will be sent when relay state changes to
ON
.
-
Send Email when relay off
: Email notifications will be sent when relay state changes to
OFF
.
-
Send Email when relay changes state
: Email notifications will be sent when relay changes
state to
ON
or
OFF
.
Note: The default setting for this field is
No Email Messages
.
page 40