Installation and Setup
WebRelay-10 Users Manual
Field Name
Event 1
Event 2
Application Description
Schedule #
0
0
Schedule 0 cannot be disabled by other events.
Description
Security ON
Security OFF
User description of event.
Start Date
Current Day
Current Day
Set to current or previous day.
Start Time
20:00:00
06:00:00
Start time in 24 hr format.
Period
1 Days
1 Days
Event occurs daily.
Days
M-F
M-F
Security system is disabled during work hours and
remains on over weekend.
Count
0
0
Event is always in effect, set to zero.
Action
turn relay on
turn relay off
Security system is controlled through a Relay 1.
Affected
1
1
Pulse Duration
n/a
n/a
The value is ignored except for a pulse action.
Schedule 1 and 2 Events – Shift alarm sounds at 8 am and 5 pm Monday through Friday, during winter
months but, shifts to 6 am start time during summer.
Field Name
Event 3
Event 4
Event 5
Event 6
Event 7
Event 8
Schedule #
1
1
1
2
2
2
Description
Summer AM
Bell
Summer AM
Bell
End Summer Winter AM
Bell
Winter AM
Bell
End Winter
Start Date
30 May
30 May
01 Sep
01 Sep
1 Sep
30 May
Start Time
08:00:00
17:00:00
00:00:00
06:00:00
03:00:00
00:00:00
Period
1 Days
1 Days
1 Days
1 Days
1 Days
1 Days
Days
M-F
M-F
All
M-F
M-F
All
Count
0
0
0
0
0
0
Action
pulse relay
pulse relay
change
schedules
pulse relay
pulse relay
change
schedules
Affected
2
2
2
2
2
1
Pulse Duration
3
3
n/a
3
3
n/a
In the above example, the Affected row applies to relays when a relay action is selected, or schedules
when a change schedule action is selected.
The security system example could also be changed to schedules 1 and 2, allowing for different hours of
operation for summer and winter schedules. Additional lunch or break bells could also be added to
schedules 1 and 2 or added in schedules 3 and 4. Events 5 and 8 would also enable and disable
schedules 1, 2, 3, and 4.
Additional equipment could be controlled by event schedules such as lighting, compressors, and
magnetic door locks.