WebRelay-10 Users Manual
Operation
3.5.2 Email Notification Setup
Email notification requires that the following fields are properly configured. See
Section 2.4.2
for a
description of each field.
Network Tab
IP Address
Subnet Mask
Gateway
Preferred DNS Server (this is required if Mail Server is entered by name and not by IP address)
Mail Server (SMTP)
User Name (If Required)
Password (If Required)
Return Email
Email 1
Email 2
Email 3
Email 4
Email 5
Note: WebRelay-10 must be power-cycled (power disconnected, then reconnected) before network
settings take effect. Only the settings on the
Network
tab require power-cycling before taking effect.
Email triggers can be generated within a BASIC script (See
Appendix G:
BASIC Scripts
), or can be
explicitly defined for each relay, input, and sensor under
Relays
,
Inputs
, and
Sensors
tabs.
The email options and recipients for each relay, sensor, or input are configured separately. Select the
the Email Option and the checkbox for the desired email recipient for each relay, sensor, or input.
Once the email settings are entered, the email functionality can be tested by entering the following
command:
http://IP address/state.xml?testEmail=1
For example, using the default IP address, enter:
http://192.168.1.2/state.xml?testEmail=1
This will cause an email message to be sent immediately. If the messages don't get through, the system
log file may have some clues to assist in diagnosing the problem (http://192.168.1.2/syslog.txt).
Xytronix Research & Design, Inc.
page 79