3500 Series Flat Panel Industrial PC
36
On a 1024 x 768 display, the stretching algorithm does not completely fill the display
horizontally or vertically. You can achieve a greater vertical text expansion by changing
to VGA mode 3* (see Note below). This is an 80 column, 25 row text mode with an ef-
fective resolution of 640 x 350. The 350 lines stretch better to fill the 768 line display.
Note
The utility disk includes the
MOD3_350.EXE utility, allowing you to
switch to VGA mode 3*. The MOD3_400.EXE utility allows you to
change the mode back to the DOS default of 3+.
Windows may come up with a blank screen when using Windows 3.X on a unit, with ex-
pansion turned on either through the BIOS setup menus or using the EXP_ON.EXE utility.
There are two available options (second option being the best) to resolve this situation:
•
Press the
CTRL
-
ALT
-
DEL
keys simultaneously. When the Windows message appears,
press any key to return to Windows. The Windows screen should appear.
•
Turn off the expansion.
•
Default to factory settings in the BIOS setup menus.
•
Use the appropriate utility as shown in the
Video Expansion Options
table.
Note
For further assistance, call Xycom Automation technical support at 1-
800-289-9266.
Mounting Considerations
This section describes issues you must address before placing the unit inside an enclosure.
Consider the following
points and precautions:
•
Select an enclosure and place the unit to allow easy access to the ports.
•
Account for the unit’s depth when choosing the depth of the enclosure.
•
Provide a NEMA 4 seal by mounting the unit in an approved enclosure with a 14
gauge (0.075"/1.9mm thick) steel or (0.125"/3.2mm thick) aluminum front face.
•
Mount the unit in an upright position.
•
Place the unit at a comfortable working level.
•
Consider locations of accessories such as AC power outlets and lighting (interior
lighting and windows) for installation and maintenance convenience.
•
Prevent condensation by installing a thermostat-controlled heater or air conditioner.
•
To allow for maximum cooling, avoid obstructing the airflow.
•
Place any fans or blowers close to the heat generating devices. If using a fan, ensure
that outside air is not brought inside the enclosure unless a fabric or other reliable
filter is used. This filtration prevents conductive particles or other harmful contami-
nants from entering the enclosure.