Freedom SW 230V Owner’s Guide
Troubleshooting
provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this
table, contact your dealer or Customer Service.
Table 4
Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution
F1
AC Output under
voltage
Escalating Auto Fault.
Must occur 3 times in 30
seconds before becoming a
manual fault.
Inverter voltage is under
200 volts.
Remove excessive load.
F2
AC Output over
voltage
Escalating Auto Fault.
Must occur 3 times in 30
seconds before becoming a
manual fault.
Inverter voltage is over 270
volts.
Check if there is an external power source
that is running parallel to the inverter’s
output.
F17
Relays Welded
Manual
AC backfeed from welded
relay.
Service required.
F18