56
Freedom SW 230V Owner’s Guide
Configuring the Freedom SW using the SCP
ACIn Settings
The
ACIn Settings
menu configures the voltage and frequency
limits for AC Input quantification range. These are the limits at
which the Freedom SW 230V considers input voltage qualified—
that is, suitable for charging batteries or powering loads. If the input
voltage is not qualified according to these settings, the Freedom SW
230V transfers from using AC input to inverting.
Figure 31
ACIn Settings Menu Screen
Table 14
Setting Defaults and Ranges
Model
Freedom SW 230V
Item
Default
Min
Max
ACIn Breaker
30A
5A
30A
ACIn Lo Volt
202V
170V
220V
ACIn Hi Volt
260V
240V
270V
FSW3524E 00: ACIn Settings
ACIn Breaker
ACIn Lo Volt
ACIn Hi Volt
ACIn Lo Freq
ACIn Hi Freq
[30A]
[170V]
[270V]
[45Hz]
[55Hz]
ACIn Lo Freq
45Hz
40Hz
48Hz
ACIn Hi Freq
55Hz
52Hz
68Hz
Table 15
ACIn Settings Menu Description
Item
Description
ACIn Breaker
Sets the ACIn (Shore) breaker size, based on the size of the breaker
installed on ACIn. The installed breaker size must not exceed the capacity
of the upstream distribution panel. The Freedom SW 230V limits the
maximum input current to this setting by derating its charging current to
an equivalent of 80% of the AC breaker size. If the connected loads
exceed the ACIn breaker setting, the AC breaker trips.
ACIn Lo Volt
Minimum acceptable input voltage level from the utility mains.
NOTE
: It is recommended to leave this setting to its default value and not
to set it to the maximum allowed. Doing so might inadvertently derate
charging power in jurisdictions where the nominal AC mains voltage or
generator output is at 220 volts.
ACIn Hi Volt
Maximum acceptable input voltage level from the utility mains.
ACIn Lo Freq
Minimum acceptable utility mains input frequency.
ACIn Hi Freq
Maximum acceptable utility mains input frequency.
Table 14
Setting Defaults and Ranges
Model
Freedom SW 230V
Item
Default
Min
Max
FSW 230V Owners Guide.book Page 56 Tuesday, August 7, 2018 9:38 AM
Summary of Contents for Freedom SW 230V 815-3524-02
Page 2: ...FSW 230V Owners Guide book Page ii Tuesday August 7 2018 9 38 AM...
Page 10: ...FSW 230V Owners Guide book Page viii Tuesday August 7 2018 9 38 AM...
Page 14: ...FSW 230V Owners Guide book Page iv Tuesday August 7 2018 9 38 AM...
Page 98: ...FSW 230V Owners Guide book Page 84 Tuesday August 7 2018 9 38 AM...
Page 103: ...FSW 230V Owners Guide book Page i Tuesday August 7 2018 9 38 AM...