44
Freedom SW 230V Owner’s Guide
Configuring the Freedom SW using the SCP
Table 6
Setting Defaults and Ranges
Model
Freedom SW 230V
Item
Default
Min
Max
Batt Type
Flooded
Flooded, Gel,
AGM, Custom
Batt Capacity
Freedom SW 2524-230
440Ah
50Ah
1000Ah
Batt Capacity
Freedom SW 3524-230
440Ah
Max Chg Rate
100%
10%
100%
Charge Cycle
3Stage
3Stage,
2StgNoFloat
ReCharge Volts
25.0V
22.0V
27.0V
ACIn Breaker
30A
5A
30A
Low Batt Cut Out
21.0V
20.0V
24.0V
Table 7
Basic Settings
Item
Description
Batt Type
Sets the system battery chemistry and type:
Flooded
,
AGM
,
Gel
, and
Custom
.
Selecting
Custom
displays the
Custom Settings
item, which
allows you to adjust the settings for each charging stage.
Batt Capacity
Selects the system battery capacity in amp hours. Setting the battery
capacity to 0 resets the charging current to its default values.
Zero Ah battery capacity implies there is no absorption exit current
criteria and absorption only exits when the absorption timer (default
3hrs, range 1min-8hr) expires.
Max Chg Rate
Sets the percentage of the maximum DC output current that is
available to the charger. The maximum DC output current for
different models is:
•
Freedom SW 2524 —65 ADC
•
Freedom SW 3524 —90 ADC
If two Freedom SW 230Vs are charging the same battery bank, set
each inverter's
Max Chg Rate
to 1/2 of the desired total charge rate.
Charge Cycle
Sets the charging method:
3-Stage
(bulk, absorption, float) or
2StgNoFloat
(bulk, absorption, no float).
ReCharge Volts
Sets the recharging volts to tell the charger to initiate charging when
the battery drains past the value setting.
ACIn Breaker
Set the breaker limit of incoming AC. See also “
Low Batt Cut Out
Low Battery Cut Out (LBCO) controls when the inverter stops
producing AC output due to a low battery voltage condition. The
inverter will stop producing AC output only after this level has been
reached for the period of time set by the
LBCO Delay
. This setting is
not temperature compensated.
FSW 230V Owners Guide.book Page 44 Tuesday, August 7, 2018 9:38 AM
Summary of Contents for Freedom SW 230V 815-3524-02
Page 2: ...FSW 230V Owners Guide book Page ii Tuesday August 7 2018 9 38 AM...
Page 10: ...FSW 230V Owners Guide book Page viii Tuesday August 7 2018 9 38 AM...
Page 14: ...FSW 230V Owners Guide book Page iv Tuesday August 7 2018 9 38 AM...
Page 98: ...FSW 230V Owners Guide book Page 84 Tuesday August 7 2018 9 38 AM...
Page 103: ...FSW 230V Owners Guide book Page i Tuesday August 7 2018 9 38 AM...