68
Freedom SW 230V Owner’s Guide
Battery Charging Reference
Figure 36
Two-Stage Charging Cycle
NOTE:
When the charge cycle is interrupted, the charger will restart charging at
the beginning of the multi-stage algorithm.
Exit Current Threshold can be effectively disabled by programming the
amp-hour capacity to the minimum. In this case, absorption will only exit
once the
Max Absorption
timer expires.
Charge current during equalize state (optional state not shown here) is
normally limited to 10% of the programmed amp-hour capacity setting. If
this setting is programmed to the maximum, the charge current during
equalize is instead limited to whatever is programmed for the max current
limit of the unit.
Synchronized charge states are active when more than one charging
device is connected in the system via the Xanbus network.
• The first unit to enter bulk, causes all other chargers to enter bulk.
• The first Freedom SW 230V to enter absorption causes all other
Freedom SW 230Vs to enter absorption.
• The last Freedom SW 230V ready to exit absorption triggers all
Freedom SW 230Vs to exit absorption and exit charge.
FSW 230V Owners Guide.book Page 68 Tuesday, August 7, 2018 9:38 AM