Original Operating Instructions
BATD0100-ES-1-480-1 (Outdoor)
Installation
O_BATD0100-ES-1-480-1_(Outdoor)_V2.2_US
Page
78
of
110
5.5.2.6 External Current Measurement Device
Required material (not include in scope of delivery):
•
Current measuring device
Procedure:
1.
Locate
the terminal strip (-X3) (Figure 29).
2.
Open
the corresponding cable ducts.
3.
Route
the cable through the cable entry grommet.
4.
Remove
the cable bridges between terminals:
o
(-X3.1) to (-X3.2)
o
(-X3.3) to (-X3.4)
o
(-X3.5) to (-X3.6)
5.
Connect
the measuring device to the following terminals:
o
For phase
L1
between (-X3.1) to (-X3.2)
o
For phase
L2
between (-X3.3) to (-X3.4)
o
For phase
L3
between (-X3.5) to (-X3.6)
6.
Close
the cable ducts.
7.
Fix
the cable with a cable clamp.