6
Commissioning
⚙
Please go to the steps below, before starting normal operation
1. ▷
Ensure all the connections are correct and wires diameter is suitable
2. ▷
Ensure that the controller DC power has fuse, controller‘s positive and negative
connected to start battery are correct
3. ▷
Emergence stop must be connected with positive of start battery via scram button’s
normal close point and fuse
4. ▷
Take proper action to prevent engine to crank disconnect (e. g. Remove the connection
wire of fuel valve). If checking is OK, make the start battery power on; choose manual
mode and controller will executive routine
5. ▷
Set controller under manual mode, press start button
, genset will start. After the
setting times as setting, controller will send signal of Start Fail; then press stop button
to reset controller
6. ▷
Recover the action of stop engine start (e. g. connect wire of fuel valve), press
again, genset will start. If everything goes well, genset will normal run after idle running
(if idle run be set). During this time, please watch for engine’s running situations and AC
generator’s voltage and frequency. If abnormal, stop genset running and check all wires
connection according to this manual
7. ▷
If there is any other question, please contact your local Woodward support
72
easYgen-400
B37884A
6 Commissioning
Released