Items
Parameters
Defaults
Description
Gen. PT
Unchecked:
Disabled
Checked: Enabled
Disabled
Notes
Access to parameters below only if »enabled«
Gen. PT primary rated
volt.
30 to 30000 V
100 V
Primary value from the used potential transformer (PT)
Gen. PT secondary rated
volt.
30 to 1000 V
100 V
Secondary value from the used potential transformer (PT)
Load Settings
[PARAMETER / Configure measurement / Load]
Items
Parameters
Defaults
Description
Load
Load CT primary rated
current
(5 to 6000)/5
500/5
The ratio of external CT
Load rated current
(5 to 6000) A
500 A
Generator’s rated current, standard of load current
Load percentage
Power (kW) /
Power (kVA)
Power
(kW)
Selects the reference for the Load %-value in Home Screen
General Measurement Settings
[PARAMETER / Configure measurement / General Measurement settings]
Items
Parameters
Defaults
Description
Voltage measuring
Voltage measuring
0: 3 Phase, 4
Wire (3Ph4W)
1: 3 Phase, 3
Wire (3Ph3W)
2: 2 Phase, 3
Wire (2Ph3W)
3: Single Phase, 2
Wire (1Ph2W)
3 Phase,
4 Wire
(3Ph4W)
3 Phase, 4 Wire (3Ph4W):
The measurement is performed line-neutral and line-line:
VL12, VL23 and VL31 VL1N, VL2N and VL3N
3 Phase, 3 Wire (3Ph3W) :
The measurement is performed line-line.
VL12, VL23 and VL31
2 Phase, 3 Wire (2Ph3W)
The measurement is performed line-neutral and line-line:
VL12
VL1N and VL2N
Single Phase, 2 Wire (1Ph2W)
The measurement is performed line-neutral:
VL1N
40
easYgen-400
B37884A
4 Configuration
4.2.3 Configure Measurement
Released