Terminals of
controller
CAN port of engine
Remark
CAN GND
-
CAN communication shielding line(connect with controller’s terminal
only)
CAN(H)
CAN(H)
Impedance 120 Ω connecting line is recommended.
CAN(L)
CAN(L)
Impedance 120 Ω connecting line is recommended.
Deutz EMR2 / Volvo EDC4
Terminals of
controller
F connector
Remark
Fuel relay output
Expand 30A relay;
battery voltage of
terminal 14 is
supplied by relay.
Fuse is 16A.
Start relay output
-
Connect to starter coil directly
-
1
Connect to battery negative pole
CAN GND
-
CAN communication shielding line(connect with controller’s terminal
only)
CAN(H)
12
Impedance 120 Ω connecting line is recommended.
CAN(L)
13
Impedance 120 Ω connecting line is recommended.
John Deere
Terminals of
controller
21 pins connector
Remark
Fuel relay output
G, J
Start relay output
D
CAN GND
-
CAN communication shielding line(connect with controller’s terminal
only)
CAN(H)
V
Impedance 120 Ω connecting line is recommended.
CAN(L)
U
Impedance 120 Ω connecting line is recommended.
MTU ADEC (Smart Module) / ECU8
Terminals of
controller
ADEC (X1port)
Remark
Fuel relay output
X1 10
X1 Terminal 9 Connected to negative of battery
Start relay output
X1 34
X1 Terminal 33 Connected to negative of battery
Terminals of controller
SMART (X4 port)
Remark
CAN GND
X4 3
CAN communication shielding line(connect to controller’s this terminal
only)
CAN(H)
X4 1
Impedance 120 Ω connecting line is recommended.
CAN(L)
X4 2
Impedance 120 Ω connecting line is recommended.