3
Installation
3.1
Mounting
Fix the controller unit using the included clips. Please see below for the overall
dimensions of the controller and the cutout dimensions of the panel.
Tighten the clips (tightening torque 0.3 Nm [2.65 lb⋅in]) in order to achieve the IP65
degree of protection.
114 mm
137 mm
44 mm
116.5 mm
90.5
mm
112
mm
88 mm
CUTOUT
Fig. 4:
easYgen-400 dimensions and cut-out
3.2
Wiring
General Notes
Battery Voltage Input
This controller can be used with batteries with a voltage range from 8 to 35 V
DC
.
The negative pole of the battery must be connected to the engine shell. The wire
between the power supply and the battery must have a cross section above 2.5 mm
2
.
If floating charge is configured: To prevent the controller from disturbing charges, do the
following:
• Directly connect the output wires of the charger to the positive and negative poles
•
of the battery.
• Connect the wires from the positive and negative pole of the battery to the positive
•
and negative input ports of the controller.
22
easYgen-400
B37884A
3 Installation
3.1 Mounting
Released