Items
Parameters
Defaults Description
0 to 400 kPa
200 kPa
When generator oil pressure higher than the
set value, starter will be disconnected. See the
installation instructions.
Disconnect OP time
0 to 20 s
0 s
The starter will be disconnected if the oil
pressure is higher than the set value for the
configured time.
NOTICE!
Disable "Firing speed RPM" if MPU is not available.
4.2.4.3
Configure TEST Run
[PARAMETER / Configure application / Configure TEST run]
Items
Parameters
Defaults
Description
Scheduled run
enabled/disabled
disabled
Notes
»enabled«: The following related settings will be taken into
account
Run mode
Off load
On load
Off load
Schedule period
Monthly
Weekly
Daily
Custom weekly
Monthly
Notes
»Custom weekly«: A table with16 x setting blocks displays,
each with ...
• Start time (weekly)
•
to select a week day
• Start time (hh:mm)
•
• Duration (m)
•
The TEST run is disabled if the duration is "0" minutes.
Max. duration is 30000 minutes.
Time (Day)
1 to 31
1
»Monthly«: Select a week day
Sunday, to
Saturday
Sunday
»Weekly«: Select a week day
Time (hour)
0 to 24 h
0 (o'clock)
Define the start time (hour)
Time (minute)
0 to 59
0
Define the start time (minute)
Duration
0 to 30000 min
30 min
Select the duration for a scheduled run
Auto start inhibit
enabled/disabled
disabled
Notes
»enabled«: The following related settings will be taken into
account
Schedule period
Monthly
Monthly
50
easYgen-400
B37884A
4 Configuration
4.2.4.3 Configure TEST Run
Released