Terminals
Fig. 5:
easYgen-400 Terminals
No.
Function
Cable
Size
Remarks
1
POWER SUPPLY
−
2.5 mm²
Connected to the negative pole of starter battery
2
POWER SUPPLY
+
2.5 mm²
Connected to positive pole of starter battery. If the wire is
longer than 30 m, use double wires in parallel. LPS Class 2
LVLE Listed DC fuse 4 A for 24 Vdc circuits is recommended.
3
FUEL Relay
Output
1.5 mm²
Relay is supplied by terminal 2.
Rated 5 Adc 24 Vdc supply output
Rated 2 Adc 24 Vdc, inductive (according to UL 6200)
4
Start Relay
Output
1.5 mm²
Relay is supplied by terminal 2.
Rated 5 Adc 24 Vdc supply output
Rated 2 Adc 24 Vdc, inductive
(according to UL 6200)
Connected to
starter coil
5
Charging
Generator D+
Input
1.0 mm²
Connect to D+ (WL) terminal.
6
Common earth
ground
1.5 mm²
Inside connect to B−.
24
easYgen-400
B37884A
3 Installation
3.2 Wiring
Released