Items
Parameters
Defaults
Description
If a type (01 or higher)
with curve is selected:
Curve can be
loaded ...
-/-
Notes
For temperature curve management and customization.
... and/or edited
(curve)
Wire break alarm
Warn
Shutdown
None
Warn
Alarm type to be released if a wire break is detected
High limit action
Immediate Stop
Cooling Down
Immediate
Stop
Reaction from the device if the high temperature alarm is
triggered.
Immediate Stop: The GCB opens and the engine stops
immediately
Cooling down: The GCB opens and the engine stops after
the configured cooldown time.
High limit shutdown
80 to 140 ºC
98 ºC (208
°F)
Release the alarm when the sensor value is identical to or
higher than this value.
High limit warning
80 to 140 ºC
98 ºC (208
°F)
Release the alarm when the sensor value is identical to or
higher than this value.
Engine heater control
enabled/disabled
disabled
Notes
»enabled«: The following related settings will be taken into
account
On
0 to 300 ºC
50 ºC (122
°F)
The engine heater control is switched on if the actual
temperature is lower than the configured threshold.
Off
0 to 300 ºC
55 ºC (131
°F)
The engine heater control is switched off if the actual
temperature is higher than the configured threshold.
Delay
0 to 3600 min
60 min
Maximum activation time from the engine heater control.
With a value of 0 the max. runtime is disabled.
Items
Parameters
Defaults
Description
Pressure
Type
00 to 14
08 SGX
╚═▷ “4.3.1 Programmable Sensors”
If a type (01 or higher)
with curve is selected:
Curve can be
loaded ...
-/-
Notes
For pressure curve management and customization.
... and/or edited
(curve)
Wire break alarm
Warn
Shutdown
None
Warn
Alarm type to be released if wire break is detected
Low limit action
Immediate Stop
Cooling Down
Immediate
Stop
Reaction from the device if the high temperature alarm is
triggered.
Immediate Stop: The GCB opens and the engine stops
immediately
43
easYgen-400
B37884A
4 Configuration
4.2.4.1.3 Configure Analog Inputs
Released