20
Force 30 Owners Manual
2015
Chimney
The flue pipe to be installed is a rising chimney.
Elbows can be used, but T’s are recommended to allow for the cleaning of the flue pipe.
For every one foot of horizontal pipe three feet of vertical pipe is required.
A draft controller should be used to allow proper flow. The draft controller must be installed as close to the
furnace as possible.
A draft inducer may be used to ensure proper draft.
The chimney draw must be between -.45 and -.30 mbars (-.18 and -.12 inches of water).
The chimney must follow all state and local codes.
The Chimney should be installed by a qualified professional.
Your Force 30 can be vented into an existing chimney as long as the chimney fits the necessary criteria, and
does not service any other appliance.
Your Force 30 has two built in power supplies for a draft controller. One is located on the Renovator Pellet
Burner. This one will switch the power on or off to the draft controller when the burner switches on or off.
The second power supply is under the front panel on the furnace. This will supply constant power to the draft
controller.
NOTE: All wiring should be done by qualified persons.
Installation
Switched Power Supply
Constant Power Supply