24. HG control parameters
Modifications must only be carried out by a recognised heating contractor or by Wolf customer
service. Incorrect operation can lead to system faults.
On the AM display module or the BM2 programming module, the factory setting for the HG parameters
can be reinstated in the Contractor menu.
To prevent damage to the heating system, cancel night setback when outside temperatures fall
below -12 °C. If this rule is not observed, ice may build up on the flue outlet which may cause injury
or material losses.
Caution
Caution
The control parameters can only be modified or displayed using the AM display module or BM2 programming
module on the boiler. For procedures, check the operating instructions of the relevant accessories.
No.
Description
Unit
Factory setting
Min
Max
HG01
Burner hysteresis
°C
15
7
30
HG02* Lower burner output, boiler
Minimum burner output
%
19
19
100
HG03
Upper burner output, DHW
Maximum burner output DHW in %
%
100
19
100
HG04
Upper burner output, heating
Maximum burner output, heating in %
%
100
19
100
HG07
Heating circuit pump run-on time
Heating circuit pump run-on time in heating mode
Min
1
0
30
HG08
Maximum boiler water temperature HZ (applicable to heating
operation) TV-max
°C
85
40
90
HG09
Burner cycle block, applicable to heating operation
Min
10
1
30
HG10
Heat source eBUS address
-
1
1
5
HG12
No function
-
-
-
-
HG13
Function, input E1
Various functions can be allocated to input E1.
-
none
div.
div.
HG14
Function, output A1 (230 V AC)
Various functions can be allocated to output A1.
-
none
div.
div.
HG 15 Cylinder hysteresis, switching differential during cylinder
re-heating
°C
5
1
30
HG16
Pump rate HC, minimum
%
25
15
100
HG17
Pump rate HC, maximum
%
100
15
100
HG19
SLP run-on time (cylinder primary pump)
Min
3
1
10
HG20
Max. cylinder heating time
Min
120
30/Off
180
HG21
Minimum boiler water temperature TK-min
°C
20
20
90
HG22
Maximum boiler water temperature TK-max
°C
90
50
90
HG25
Boiler excess temperature during cylinder heating
°C
10
1
30
HG33
Burner hysteresis runtime
Min
10
1
30
HG34
eBUS feed
-
Auto
Off
ON
HG37
Pump control type (constant / linear / dT)
-
dT
div.
div.
HG38
Set dT, pump control unit (dT)
°C
20
0
40
HG39
Soft start time
Min
3
0
10
HG40
System configuration (see chapter "Parameter description")
-
1
div.
div.
HG41
Speed ZHP DHW
%
100
15
100
HG42
Header hysteresis
°C
5
0
20
HG43
No function
-
-
-
-
HG44
No function
-
-
-
-
HG45
No function
-
-
-
-
HG46
Header excess boiler water temperature
°C
6
0
20
* HG02 controls the fan speed 19 % - fan speed corresponds to 17 % burner output.