25. Parameter description
Parameter HG07
Run-on time, heating circuit pump
If there is no more heat demand from the heating circuit, the feed/heating circuit
pump ZHP will run on in accordance with the set time to prevent a boiler safety
shutdown at high temperatures.
Parameter HG08
Maximum boiler water temperature
HZ TV-max.
This function limits the boiler water temperature upwards in heating mode, and
the burner shuts down. This parameter has no function during cylinder heating,
and the boiler water temperature may also be higher during this time. "Reheating
effects" can result in the temperature being slightly exceeded.
Parameter HG09
Burner cycle block
Each time the burner is shut down in heating mode, it will be blocked for the
duration of the burner cycle block. The burner cycle block is reset by switching
the ON/OFF switch OFF and ON or by briefly pressing the reset button.
Parameter HG10
eBUS address of the heat source
If multiple heat sources are controlled in one heating system with a cascade
module, addresses must be allocated to the heat sources. Each heat source
requires its own eBUS address in order to communicate with the cascade
module. The activation sequence of the heat sources can be set in the cascade
module.
Please note: Duplicated addresses lead to malfunctions of the heating system.
Factory setting:
see table chap. 24
Control unit parameters
Individual settings: ________
Factory setting:
see table chap. 24
Control unit parameters
Individual settings: ________
Factory setting:
see table chap. 24
Control unit parameters
Individual settings: ________
Factory setting:
see table chap. 24
Control unit parameters
Individual settings: ________