3063772_201507
30. Checking the gas supply pressure
Check the gas supply pressure (gas flow pressure)
Work on gas components must only be
performed by a licensed gas fitter. Work
that is carried out incorrectly may lead to
gas escaping, resulting in a risk of
explosion, suffocation or poisoning.
• Switch ON/OFF switch on the appliance to OFF.
• Release the plug at the test nipple with two turns.
• Slowly open the gas shut-off valve.
• Bleed off escaping gas via a hydraulic seal
until no more air escapes.
• Connect the differential pressure tester at the
pressure test nipple to "+", with "-" against
atmosphere.
• Switch the ON/OFF switch to ON.
After starting the boiler, check the supply pressure
at the differential pressure tester.
• Switch the ON/OFF switch to OFF. Close the gas
shut-off valve.
• Remove the differential pressure tester.
Re-seal the test nipple with the plug.
• Open the gas shut-off valve.
• Check the test nipple is gas-tight.
• Refit the burner hood.
If any screws are not tightened, there is a
danger of gas escaping, leading to a risk
of explosion, suffocation or poisoning.
Pressure test nipple
Country
Appliance
category
Supply pressure
in mbar
Natural
gas
Natural gas
Nom. Min. Max.
EN
I2ELL
20
18
25
AT, BG, CH, CZ, DK, EE,
ES, FI, GB, GR, HR, IE,
IS, IT, LT, LV, NO, PT,
RO, RU, SE, SI, SK, TR
I2H
20
18
25
LU
I2E
20
18
25
PL
I2ELw
20
18
25
BE
I2E(R)
20/25
18
30
FR
I2Esi
20/25
18
30
HU
I2HS
25
18
30
NL
I2L
25
18
30
Countries, gas categories and connection
pressures
If the supply pressure is outside the specified range,
adjustments must not be carried out and the boiler
must not be started.
Caution