Pin assignment on the connector
A
Socket of the reader unit
B
Connector on door or wall
13.
Connect the relay of the reader with the connector on the door or
wall.
Wire the reader unit
1
Supply voltage
2
Leads are connected
14.
Connect the reader unit to the control unit.
The communication between the reader unit and control unit
takes place via a RS-485 interface:
–
A shielded cable must be used for RS-485 data lines of the reader
unit and the inputs of the control unit.
–
For cable lengths over 3 m, terminate the BUS close to the
cable ends with a resistor between A and B. Suitable values are
between 470 and 220 ohm(#1/8 W)
–
Connect the shielding to earth potential at a point. If the control
unit is installed in a distribution or flush-mounted box, only
voltages below 40 V must be present there.