16
60706-211/J
Function
Factory
Setting
Dip
Switch
Dip
Actuator
Actuator
Position
Clock
Battery
Off
S2
10
On (up)
Off (down)
Exerciser
Off
S1
7
On (up)
Off (down)
With load
or without
load
Without
Load
S1
8
With (up)
Without
(down)
SETTING THE EXERCISER
Press and hold (5 seconds) the Set Engine Exerciser button.
The exercise period occurs immediately and at the same
time weekly thereafter. The status light below the button
blinks during the exercise period (including cool down). The
light stays on to indicate that the exerciser has been set. If
the light is off, the exerciser has not been set.
CANCELING AN ACTIVE EXERCISE PERIOD
Press the Bypass Time Delay button to stop an exercising
generator. If exercise with load is set, the ATS retransfers the
load to the utility, then stops the generator after cooldown.
WARNING
With a total power failure (utility power fails and the
generator fails to start and run), the exerciser must be reset
after the power is restored.
The ASCO 185 has settings that can be changed for various
applications. The dipswitch options are explained in the
ASCO 185 Operator’s Manual.
This completes your installation and unit testing. ALWAYS
leave the system in automatic mode unless servicing the
unit. For automatic operation, the auto mode icon must be
displayed on the engine control
module display.
CUSTOMER CONNECTION AREA
CUSTOMER DC
CONNECTIONS
TO 2-WIRE
AUTOMATIC
TRANSFER
SWITCH 1 &
22/23
ENGINE
CONTROL
MODULE
ASSEMBLY
START &
FUEL RELAYS
LOCATED IN
BACK
CUSTOMER TO
CONNECT TO
120V UTILITY
LINE TO POWER
BATTERY
TENDER AND
OPTIONAL
ENGINE
HEATER
CUSTOMER
GENERATOR
OUTPUT
CONNECTIONS
TO EMERGENCY
TRANSFER SWITCH
EMERGENCY
STOP
CONTACTS
PROVIDED
FOR REMOTE
EMERGENCY
STOP SWITCH
UNIT WILL NOT
RUN IF JUMPER
IS REMOVED
BATTERY
TENDER
CUSTOMER
EARTH GROUND
CONNECTED HERE
AS REQUIRED
TORQUE TO 16 IN
LBS RATED FOR 4
TO 10 AWG WIRE -
85 AMPS
TORQUE TO 16
IN LBS RATED
FOR 4 TO 10
AWG WIRE - 85
AMPS
TORQUE
SCREWS TO 9.6
IN LBS. 14 TO 16
AWG COPPER
WITH LUGS
Summary of Contents for PSS8B2F
Page 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...
Page 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...
Page 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...
Page 24: ...24 60706 211 J AC WIRING SCHEMATIC...
Page 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...
Page 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...