18
60706-211/J
DSE 3110
FRONT PANEL CONFIGURATION
ACCEPT BUTTON
DECREASE VALUE/
NEXT ITEM BUTTON
NEXT PAGE BUTTON
INCREASE VALUE/
NEXT
ITEM
BUTTON
This configuration mode allows the operator limited
customizing of the way the module operates. Use the
module’s navigation buttons to traverse the menu and
make value changes to the parameters.
ACCESSING THE FRONT PANEL
Press
and simultaneously. This display shows the
configuration icon: The first parameter is also displayed.
EDITING A PARAMETER
1. Press to select the required ‘page’ as detailed below.
2. Press to select the next parameter or to select
the previous parameter within the current page.
3. When viewing the parameter to be changed, press .
The value begins to flash.
4. Press or to adjust the value to the requested
setting.
5. Press to save the current value. The value stops
flashing.
6. Press and hold the button to exit the editor, the is
removed from the display.
NOTE:
Values representing pressure will be displayed in Bar.
Values representing temperature are displayed in degrees
Celsius.
When adjusting values in the front panel editor, a “press
and hold” of the increment button will cover the full
range of the item being adjusted (min to max) in under 20
seconds.
When the editor is visible, it will exit after 5 minutes of
inactivity for security.
DSE 3110 FAULT CODES
Auxiliary inputs can be user configured and will
display he message as written by the user.
Fail to Start. The engine has not fired after the
preset number of start attempts.
Fail to Stop. The module has detected a condition
that indicates that the engine is running when it
has been instructed to stop.
NOTE:- ‘Fail to Stop’ could indicate a faulty oil
pressure sensor - If engine is at rest, check oil
sensor wiring and configuration.
Low Oil Pressure. The module detects that the
engine oil pressure has fallen below the low oil
pressure pre-alarm setting level after the Safety
On timer has expired.
Engine High Oil Temperature. The module
detects that the engine oil temperature has
exceeded the high engine temperature pre-alarm
setting level after the Safety On timer has expired.
Underspeed - The engine speed has fallen below
the underspeed pre-alarm setting.
Overspeed - The engine speed has risen above
the overspeed pre-alarm setting.
Battery Under/Over Voltage. The DC supply has
fallen below or risen above the low/high Volts
setting level.
Generator Under Voltage - The generator output
voltage has fallen below the pre-set pre-alarm
setting level.
Generator Over Voltage - The generator output
voltage has risen above the pre-set pre-alarm
setting after the Safety On timer has expired.
Generator Under Frequency - The generator
frequency has fallen below the pre-set pre-alarm
setting after the Safety On timer has expired.
Generator Over Frequency - The generator
output frequency has risen above the pre-set pre-
alarm setting
Summary of Contents for PSS8B2F
Page 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...
Page 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...
Page 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...
Page 24: ...24 60706 211 J AC WIRING SCHEMATIC...
Page 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...
Page 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...