4
60706-211/J
SPECIFICATIONS
GENERATOR
STANDBY
Fuel
Watts*
Volts
Amps
HZ
PH
RPM
LP
8,400
120/240 35
60
1
3600
NG
7,600
120/240 32
60
1
3600
MAIN
CIRCUIT
BREAKER
35
AMP
PRIME
Fuel
Watts*
Volts
Amps
HZ
PH
RPM
LP
6,720
120/240 28
60
1
3600
NG
6,080
120/240 25
60
1
3600
MAIN
CIRCUIT
BREAKER
25
AMP
Derate 3.5% per 1000 feet elevation above sea level.
For prime power option, derate 30% and note the circuit
breaker derates to 25 Amp.
FUEL CONSUMPTION
Natural Gas
1000 BTU/FT³
LP Vapor
2520 BTU/FT³
CF/HR*
132
63
BTU/HR*
132,000
158,760
GAL/HR*
N/A
1.6
*Based on full load operation.
LP TANK SIZING
Tank Temperature
Tank Size
60° F (16° C)
150 Gallons
32° F (0° C)
150 Gallons
0° F (18° C)
250 Gallons
-20° F (-29° C)
500 Gallons
ENGINE
Make Briggs
&
Stratton
Model
Vanguard
Displacement 570
CC/OHV
Cylinders/Sleeves
V-Twin/Cast Iron
Ignition
Electronic
Governor
Mechanical
Exhaust
Critical
Grade,
Glass-pack
See engine manual for additional information
Summary of Contents for PSS8B2F
Page 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...
Page 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...
Page 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...
Page 24: ...24 60706 211 J AC WIRING SCHEMATIC...
Page 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...
Page 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...