PREPARING THE UNIT

UNPACKING

CAUTION: EQUIPMENT DAMAGE

When you unpack your new generator, be sure to remove 

all of the information sheets and manual from the carton.

1. As you receive your unit, it is critical to check it for any 

damage. If any damage is noted, it is always easiest to 

refuse the shipment and let WINCO take care of the freight 

claim. If you sign for the unit, the transfer of the ownership 

requires that you file the freight claim

2. Before proceeding with the preparations of your new 

generator for operation, take a couple of minutes to ensure 

the unit you have received is the correct model and review 

the specification pages in this manual to ensure that this 

unit meets your job requirements.

CAUTION

These units are shipped with oil. Be sure to check oil levels 

before operating. See engine manufacturer’s instruction 

manual for recommended oil requirements before initial 

starting.

LUBRICATION

Before starting the engine, fill the crankcase to the proper 

level with a good quality oil. The recommended grade oil 

and quantity of oil required is listed in the engine operator’s 

manual and under the service tab in this manual. This unit 

was shipped with most of the oil removed.

The engine normally holds 48 ounces (1.5 quarts) of oil.

Since there is some trapped in the engine, when filling the 

crankcase the first time, use the dipstick (‘A’ in following 

image) to ensure that you do not over fill the crankcase. The 

full oil level mark on the dipstick is depicted in the following 

image as ‘B’.

Oil is added to the engine by removing the oil cap and 

adding oil at this point. After filling the crankcase to the 

proper level, be sure you properly tighten the oil fill cap (‘C’).

NOTE:

 This engine generator must be on a level surface 

before you check or add oil to the system.

The necessity of using the correct oil and keeping the 

crankcase full cannot be overemphasized. Engine failures 

resulting from inadequate or improper lubricant are 

considered abuse and not covered by the generator or 

engine manufacturer’s warranty.

OIL RECOMMENDATIONS

Outdoor temperatures 

determine the proper oil

viscosity for the engines.

Winco recommends our

5W-30 fully synthetic oil 

to give you excellent 

protection in cold 

temperatures while 

maintaining excellent 

performance in warmer weather.

OIL ALERT SYSTEM

This generator is equipped with a low oil shutdown system. 

This Briggs & Stratton engine uses an oil pressure switch 

system. If the oil level drops below a certain point the low 

oil module on the engine will shut it down. This low oil 

warning system will automatically stop the engine before 

the oil level reaches critical danger point. This feature is 

designed to prevent costly repairs and downtime.

CAUTION: EQUIPMENT DAMAGE

Allowing the engine to shutdown repeatedly on low oil 

level may cause excessive wear which can be cumulative. 

Summary of Contents for PSS8B2F

Page 1: ...o contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHA...

Page 2: ...WITCH ENGINE GENERATOR SET ENGINE MAINTENANCE MAINTENANCE SCHEDULE TROUBLESHOOTING 22 OUTLINE DRAWING 23 PAD LAYOUT DRAWING 24 AC WIRING SCHEMATIC 24 AC AND DC GENERATOR SCHEMATIC 25 SOLAR CONTROL PAN...

Page 3: ...t must be mixed with fresh air A Operate only in well ventilated areas B Never operate indoors including attached garages C Never operate the unit in such a way as to allow exhaust gases to seep back...

Page 4: ...er option derate 30 and note the circuit breaker derates to 25 Amp FUEL CONSUMPTION Natural Gas 1000 BTU FT LP Vapor 2520 BTU FT CF HR 132 63 BTU HR 132 000 158 760 GAL HR N A 1 6 Based on full load o...

Page 5: ...ment The ATS also contains the power failure sensing circuitry necessary to start and stop the engine generator set The transfer switch is also equipped standard with a 3 second start delay and a 15 s...

Page 6: ...crankcase the first time use the dipstick A in following image to ensure that you do not over fill the crankcase The full oil level mark on the dipstick is depicted in the following image as B Oil is...

Page 7: ...satisfactory system installation The information in this manual is offered only as a guide to finalizing your installation plans WARNING PERSONAL INJURY The enclosures on these units can become very...

Page 8: ...rimary to the low pressure regulator Consult your local fuel supplier for your exact requirements The appropriate line size from the following table is then installed from the low pressure regulator t...

Page 9: ...Natural gas Ref 2 3 4 Unit off Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Starting Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz No load Line PSI 7 11 in 4 6 oz 7 11 in 4 6 oz Full load Line PSI 7 11 in 4 6 oz...

Page 10: ...sh off immediately with water 3 If electrolyte contacts the eyes flush immediately and thoroughly with water Seek immediate medical attention 4 Spilled electrolyte is to be washed down with an acid ne...

Page 11: ...be fused for 15 Amps Terminal block connections have been provided in the customer connection area of the engine generator set See following diagram NOTICE The battery tender is not intended to recha...

Page 12: ...als L3 L7 The neutral leads from all three locations are connected to the isolated terminal lugs on the sidewall of the cabinet This terminal block is labeled NEUTRAL and the terminal lugs are mounted...

Page 13: ...through 9 These terminals will accept 22 14 AWG stranded wire It is recommended that you use 16 AWG for distances up to 200 feet You need to run two 2 wires from the engine generator set to the transf...

Page 14: ...y Deep Sea Electronics Model 3110 is used on this generator set See following picture and look for more information stated within this manual MANUAL OPERATION Press and release the red Stop Reset butt...

Page 15: ...hanging the exercise without a load will be discussed later Be sure that conditions are safe to do this operation BYPASS TIME DELAY Use this button to cancel the active time delay or exercise period s...

Page 16: ...art and run the exerciser must be reset after the power is restored The ASCO 185 has settings that can be changed for various applications The dipswitch options are explained in the ASCO 185 Operator...

Page 17: ...17 60706 211 J SEQUENCE OF OPERATION UTILITY FAILURE...

Page 18: ...Auxiliary inputs can be user configured and will display he message as written by the user Fail to Start The engine has not fired after the preset number of start attempts Fail to Stop The module has...

Page 19: ...The fault must be removed and the Stop Reset button pressed to reset the module The icon will appear flashing in the display MODULE DISPLAY TIMER ICON When the module is controlling the engine startin...

Page 20: ...il level must always be checked before the engine is started Refer to page 7 of this manual for instructions on checking the oil level Take care to remove any dirt or debris from around the oil plug b...

Page 21: ...ked up engine generator set 9 Defective starter fuel solenoid relays ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4 Defe...

Page 22: ...22 60706 211 J 36 50 28 00 29 75 36 00 27 375 28 375 OUTLINE DRAWING...

Page 23: ...23 60706 211 J PAD LAYOUT DRAWING 11075 00 20 60706 211 ENGINE GENERATOR SET PAD LAYOUT...

Page 24: ...24 60706 211 J AC WIRING SCHEMATIC...

Page 25: ...25 60706 211 J 11075 00 22 60706 211 AC AND DC GENERATOR SCHEMATIC AC AND DC GENERATOR SCHEMATIC...

Page 26: ...26 60706 211 J EXTERNAL RECEPTACLE ASSEMBLY IF EQUIPPED SOLAR CONTROL PANEL IF EQUIPPED...

Page 27: ...27 60706 211 J SOLAR PANEL ASSEMBLY IF EQUIPPED...

Page 28: ...does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WINCO does not warrant engines Engines a...

Reviews: