Installation and operating instructions Wilo-CC-System
37
3.3.3.2
Peak load pump
*
(Page 1)
Display/setting of switching
on and off pressure, time
delays for switching on and off
for the peak load pumps
(All settings in % of 1. setpoint)
p
SLon
[%]
p
SLoff
[%]
t
SLon
[s]
t
SLoff
[s]
**
**
**
**
75
110
3
3
*
(Page 2)
Display/Adjustment of switch-
ing on and off-pressures and
time delays for peakload
pumps (
All settings in bar)
none
-
3.3.3.3
PID-Controller
*
Adjustment of proportional
action coefficient, integral
action time and derivative
action time of PID-controller
Ability of automatic adaption
to installation with the softkey:
Proportional action
coefficient k
P
Integral action time t
I
[s]
Derivative action time
t
D
[s]
AutoPID
**
**
**
***
2,5
0,5
0,1
-
3.3.4
Pump parameter
*
Call of menues for the setting
of number of pumps and the
parameters for pumpchange
and pumpkick
none
-
3.3.4.1
Number of pumps
*
Setting of the number of
pumps (1...6)
Number of pumps
with/without reserve
pump
**
**
Installation
specific
Installation
specific
3.3.4.2
Pump change
*
Fixing of the changing mode
for pumpchange (running
hours, when switching on,
cyclic) and the times for
changings.
Ability to pre-select the
baseload pump
Operating hours [h]
Cycle time for pump
change [min]
No. of preselected
pump
**
**
**
24
360
0
Menue
-No.
Display
Description
Parameter settings/
Functions
Factory-
settings
visible for
changeable by
User 1 and higher:
*
User 1 and higher:
*
Call
User 2 and higher:
**
User 2 and higher:
**
by:
Service:
***
Service:
***