English
34
Wilo AG 03/2006
2.2
Simulation
***
Switching on/off of simula-
tionsmode (Testrun of panel
without sensor). Variation of
simulated pressure value by
the softkeys
Simulation ON/OFF
Simulation pressure
***
***
OFF
-
3
Main menue
*
Call of Login/Logout, fault-
messages, parametersettings,
passwordsettings and site
information
none
-
3.1
Login/Logout
Input of passwords for Login
(User1, User2, Service), Display
of Login-Status, ability to Log-
out (Auto-Logout after 60
Minutes)
Passwort input
-
3.2
Fault messages
*
Display of recent fault mes-
sages (if there are more than
one, messages are shown
cyclic one by one), local reset
of faults, Call of list of fault
messages and SMS-settings
Reset
*
-
3.2.1
Fault messages
*
Display of fault history (35
messages) with timestamp;
Browsing via so/-
Browsing of failure
messages
*
-
3.2.2
SMS-adjustments
*
(page 1 - SMS-Messager) Dis-
play of SMS-Status
Reset
**
-
*
(page 2 - Messagepriority)
Fixing of priorities (0...4) for
maximum 4 phonenumbers
and the time for the send
repeat.
Fixing of acknowledgement
obligation
Priority
of phone number 1
Priority
of phone number 2
Priority
of phone number 3
Priority
of phone number 4
Time between repeats
[min]
**
**
**
**
**
1
0
0
0
15 min
Menue
-No.
Display
Description
Parameter settings/
Functions
Factory-
settings
visible for
changeable by
User 1 and higher:
*
User 1 and higher:
*
Call
User 2 and higher:
**
User 2 and higher:
**
by:
Service:
***
Service:
***