36
Wilo AG 03/2006
3.3.2.2
2. Set point
*
Setting of 2. setpoint and
switching times between set-
points 1 and 2
p
Set2
[bar]
t
p2on
[Std:Min]
t
p2off
[Std:Min]
**
**
**
0,0
00:00
00:00
3.3.2.3
Limit values
*
Input of maximalpressure
(overpressurecontrol) and
minimalpressure (pipe-break
control). For this limits a hys-
teresis and a time delay for the
alarm can be fixed
p
max
[bar]
p
min
[bar]
p
Hyst
[bar]
t
Hyst
[s]
**
**
**
**
Installation
specific
3.3.2.4
Sensor
*
Selection of pressure sen-
sortype (measuring range) and
reaction of panel in case of
sensorfailure (Switching "off"
all drives, operation of all drives
with maximum speed, opera-
tion of one pump with prese-
lected speed - please see
Menue 3.3.5 page 2)
Sensor
Operation in case of
sensorfault
**
**
16
Stop
3.3.3
Controller parameter
*
Call of menues for adjustment
of parameters for baseload and
peakload switching, adjust-
ment of PID-controller
none
-
3.3.3.1
Base load pump
*
(Page 1)
Base load pump
Display/
Setting of:
• On and off pressure for base
load pump in nornal opera-
tion
• Switching off pressure
• Delay for base load pump
when operating without FC.
(All settings in % of 1. set-
point)
p
GLon
[%]
p
GLoff
[%]
p
GLoff2
[%]
t
GLoff
[s]
**
**
**
**
90
105
110
10
*
(Page 2)
Base load pump
Display/
Setting of:
• On and off pressure for base
load pump in nornal opera-
tion
• Switching off pressure
• Delay for base load pump
when operating without FC.
keine
-
Menue
-No.
Display
Description
Parameter settings/
Functions
Factory-
settings
visible for
changeable by
User 1 and higher:
*
User 1 and higher:
*
Call
User 2 and higher:
**
User 2 and higher:
**
by:
Service:
***
Service:
***