Wilo AG 03/2006
3.3.4.3
Pump kick
*
Adjustment of the pumpkick
intervall and the duration of
testrun.
Pumpkick can be forced by the
softkey:
Each stroke of the key will start
the pump for the adjusted
testrun duration. Pumps will be
count up.
Test run intervall [h]
Test run duration [s]
Test
**
**
*
6
10
-
3.3.5
FC parameter
*
(Page 1)
Adjustment of the maximal and
minimal output frequencies
and ramp times of the frequen-
cyconvertors.
f
max
[Hz]
f
min
[Hz]
t
Ramp+
[s]
t
Ramp-
[s]
FC type
**
**
**
**
***
50
20
5
5
Installation
specific
*
(Page 2)
Adjustment of FC-frequencies
for overpressure and pressure
break avoidance in the
moment of peakloadswitching
on and off.
Setting of fixed output fre-
quency for controlled pump in
case of sensorfault.
f
Peak+
[Hz]
f
Peak-
[Hz]
f
Not
[Hz]
**
**
**
20
50
40
3.3.6
FC status
*
(Page 1 - status messages)
Display of statusmessages for
busconnection and frequency-
convertor.
none
-
*
(Page 2 – FC faults)
Display of alarm messages of
FC (Voltage, current, tempera-
ture)
none
-
3.3.7
Time
*
Adjustment of real time clock
(time, date)
Time [hh:mm:ss]
Date: [jj.mm.tt]
-
-
Menue
-No.
Display
Description
Parameter settings/
Functions
Factory-
settings
visible for
changeable by
User 1 and higher:
*
User 1 and higher:
*
Call
User 2 and higher:
**
User 2 and higher:
**
by:
Service:
***
Service:
***