10.
Faults, causes and remedies
WARNING! Danger due to electrical voltage!
Dangers from electricity must be ruled out.
The pump must be voltage-free before com-
mencing electrical work and secured against
unintended reactivation.
WARNING! Risk of burns!
If the water temperature and the system pres-
sure are high, close the stop valve on the suction
side and on the pressure side.
The pump must cool down first
.
Fault
Cause
Remedy
The pump is not running
No power supply
Check fuse protection, wiring and
connections
Motor protection has interrupted the
power supply
Avoid overloading the motor
The pump runs but does not reach its
duty point
Incorrect direction of rotation
Check the direction of rotation and correct
as necessary
Pump components are blocked by foreign
objects
Check the pump and clean it
Air inclusion in the pump
Seal the suction port
Suction line too narrow
Install a larger suction line
The stop valve is not sufficiently open
Fully open the stop valve
The pump does not pump evenly
Air in the pump
Vent the pump and ensure that the
suction line is sealed.
If necessary, start the pump for 20
to 30 s. Open the venting screw so that
the air can escape. Close the venting
screw and repeat the procedure as often
as required
The pump vibrates or is loud
Foreign object in the pump
Remove the foreign object
The pump is not properly attached to the
ground
Tighten the anchor screws
Bearing damaged
Contact Wilo customer service
The motor has overheated, motor
protection has been activated
One phase is interrupted
Check fuse protection, wiring and
connections
Fluid temperature too high
Maximum fluid temperature
Foreign object in the pump
Remove the foreign object
Bearing damaged
Contact Wilo customer service
The delivery rate is inconsistent
In “Constant pressure” or “Variable pres-
sure” mode, the pressure sensor is not
adapted
Install a sensor with a compliant pressure
scale and precision
In “Constant pressure” or “Variable
pressure” mode, the pump does not
switch off when the delivery rate is
zero
The non-return valve is not impermeable
Clean or change it
The non-return valve is not adapted
Replace it with an adapted non-return
valve
The tank does not have enough capacity
for the installation
Change it or add another to the installation
If the fault cannot be resolved, please
contact Wilo customer service
.
English
WILO SE 04/2020
Summary of Contents for Multivert MVISE 200
Page 2: ......
Page 3: ...HC 0 5 m HC 2 m 100 mm Mini 10 9 7 6 4 2 1 5 8 OU OR 5 3 11 Fig 1...
Page 4: ...12 14 13 12 14 13 8 OU OR Fig 2...
Page 6: ...Fig 6 Fig 5 16 15...
Page 37: ...37 Einbau und Betriebsanleitung Wilo Multivert MVISE 3G...
Page 67: ...67 Installation and operating instructions Wilo Multivert MVISE 3G...
Page 97: ...97 Notice de montage et de mise en service Wilo Multivert MVISE 3G...
Page 127: ...127 Inbouw en bedieningsvoorschriften Wilo Multivert MVISE 3G...
Page 157: ...157 Instrucciones de instalaci n y funcionamiento Wilo Multivert MVISE 3G...
Page 158: ...158 1 1 1 2 2 1 2 2 2 3 2 4 2 5 WILO SE 04 2020...
Page 159: ...159 Wilo Multivert MVISE 3G 2 6 2 7 2 8 4 3 30 C 60 C 4 4 1...
Page 163: ...163 Wilo Multivert MVISE 3G 5 2 6 2 2 10 7 7 1 7 2 Fig 1 10...
Page 164: ...164 7 3 M10 20 M12 30 7 4 5 3 kW 1 1 2 M25 Ext Off Aux kW 1 1 2 WILO SE 04 2020...
Page 165: ...165 Wilo Multivert MVISE 3G gF RCD 30 25 A B 2...
Page 176: ...176 Fig A2 EASY EXPERT EXPERT Fig A4 Information EASY Fig A3 WILO SE 04 2020...
Page 180: ...180 Fig A5 Information SSM SBM Ext Off INFORMATION 4000 WILO SE 04 2020...
Page 181: ...181 Wilo Multivert MVISE 3G 9 2 ON 7 0 0 0 2 OFF A1 1...
Page 182: ...Wilo 182 10 20 30 Wilo Wilo WILO SE 04 2020...
Page 183: ...183 Wilo Multivert MVISE 3G 9 2 SBM 5 7 6 0 3 1 2 3 SSM 1 6 6 24 SBM 24 SBM SSM 1 2 3 4 5 6 24...
Page 185: ...185 Wilo Multivert MVISE 3G 10 2 6 0 0 0 24 1 6 300...
Page 186: ...186 11 Wilo www wilo com 12 www wilo recycling com WILO SE 04 2020...
Page 187: ...187 Wilo Multivert MVISE 3G...
Page 217: ...217 Kurulum ve al t rma talimatlar Wilo Multivert MVISE 3G...
Page 218: ...218 1 1 1 2 2 1 2 2 2 3 2 4 IEC VDE WILO SE 04 2020...
Page 219: ...219 2 5 IEC VDE 2 6 2 7 2 8 4 3 30 C 60 C 4 Wilo Multivert MVISE 3G...
Page 223: ...223 7 7 1 7 2 Fig 2 10 Wilo Multivert MVISE 3G...
Page 224: ...224 7 3 M10 20 M12 30 7 4 5 1 1 2 M25 WILO SE 04 2020...
Page 225: ...225 2 Ext Off Aux gF FI 30 25 B 1 1 2 M20 M12 M25 M12 M16 Wilo Multivert MVISE 3G...
Page 236: ...Fig A2 EASY EXPERT EXPERT Fig A4 EASY Fig A3 236 WILO SE 03 2019 WILO SE 04 2020...
Page 240: ...240 Fig A5 Information SSM SBM Ext Off INFORMATION 4000 WILO SE 04 2020...
Page 241: ...241 DIP 2 ON 7 0 0 0 DIP 2 OFF 9 Wilo Multivert MVISE 3G...
Page 242: ...242 10 Wilo 20 30 Wilo Wilo WILO SE 04 2020...
Page 245: ...245 10 2 6 0 0 0 24 1 6 300 Wilo Multivert MVISE 3G...
Page 246: ...246 11 Wilo 12 www wilo recycling com WILO SE 04 2020...
Page 254: ......
Page 255: ......
Page 256: ......