53
Installation and operating instructions –
Wilo-Multivert MVISE 3G
English
NOTICE: If the pump is provided alone, and not
integrated into a system installed by us, the con-
figuration mode upon delivery is the “speed stage
control” mode
.
“Speed stage control” mode (Fig. 1)
• The duty point is obtained by manually adjust-
ing the speed stage via the menus or using an
external command signal for the speed stage
expressed in %.
• For entry into service, the motor speed stage
should be set at 2400 rpm.
“Constant pressure: pc” mode (Fig. 2)
• In “p-c” mode, the converter maintains a con-
stant pressure at the pump discharge irrespective
of the delivery rate required by the installation.
•
The duty point is defined manually via the menus
or an external signal.
• This mode can be accessed when the
open hydraulic loop parameter is selected in
menu 5.7.8.0.
• A relative pressure sensor is used for control
(sensor: accuracy: ≤
1 %; using between 30 %
and 100 % of the measuring range).
• For entry into service, the set pressure should be
set at 60 % of the pump’s maximum pressure.
“Δp-c” mode (Fig. 2)
•
In “Δp-c” mode, the converter maintains a con
-
stant differential pressure (generated by the
pump) irrespective of the delivery rate required
by the installation.
• The differential pressure is defined manually via
the menus or via an external signal.
• This mode can be accessed when the
closed hydraulic loop parameter is selected in
menu
5.7.8.0.
• A differential pressure sensor is used for control
(sensor: accuracy: ≤
1 %; using between 30 %
and 100 % of the measuring range).
• For entry into service, the set pressure should be
set at 60 % of the pump’s maximum pressure.
Pc
P
at m
Pr
essur
e
Time
Δp-c
Δp-c
Pr
essur
e
Time
“Variable pressure: Δp-v” mode
(Fig. 2)
•
In “Δp-v” mode, the converter changes the dif
-
ferential pressure of the pump in a linear manner,
in line with the delivery rate required by the
installation.
• The duty point (Pset) is defined manually via the
menus or an external signal.
•
The duty point at a zero delivery rate (%Pset) is
defined manually via the menus.
•
This mode includes zero delivery rate detection
that switches off the pump.
• A differential pressure sensor is used for control
(sensor: accuracy: ≤ 1 %; using between 30 %
and 100 % of the measuring range).
• For entry into service, the set pressure should be
set at 60 % of the pump’s maximum pressure.
• This mode can be accessed when the
closed hydraulic loop parameter is selected
in menu 5.7.8.0.
“PID control” mode
• The converter enables control with another type
of sensor (temperature, delivery rate, etc.) via
control of the PID (proportional integral differen-
tial control).
•
The duty point is expressed as a percentage of
the measurement range of the sensor used. This
point is defined manually via the menus or via an
external control signal.
8.3.7
Menu description
List of menus (Fig.
A5)
<
1.0.0.0
>
Setpoint setting
<
2.0.0.0
>
Operating mode setting
<
3.0.0.0
>
On/Off pump setting
<
4.0.0.0
>
“Information” menu
Reading the pump parameters
<
5.0.0.0
>
“Service” menu
Access to the pump parameter
settings
<
6.0.0.0
>
Error acknowledgement
If one or more malfunctions occur, the
malfunction page will appear. The let
-
ter “E” followed by a three-figure code
will appear (see section 10).
<
7.0.0.0
>
Access lock
The “Access lock” can be accessed if
DIP switch 2 is in the ON position.
CAUTION! Risk of property damage!
Incorrect setting changes may cause pump oper-
ation faults which may lead to damage of the
pump or installation.
Summary of Contents for Multivert MVISE 200
Page 2: ......
Page 3: ...HC 0 5 m HC 2 m 100 mm Mini 10 9 7 6 4 2 1 5 8 OU OR 5 3 11 Fig 1...
Page 4: ...12 14 13 12 14 13 8 OU OR Fig 2...
Page 6: ...Fig 6 Fig 5 16 15...
Page 37: ...37 Einbau und Betriebsanleitung Wilo Multivert MVISE 3G...
Page 67: ...67 Installation and operating instructions Wilo Multivert MVISE 3G...
Page 97: ...97 Notice de montage et de mise en service Wilo Multivert MVISE 3G...
Page 127: ...127 Inbouw en bedieningsvoorschriften Wilo Multivert MVISE 3G...
Page 157: ...157 Instrucciones de instalaci n y funcionamiento Wilo Multivert MVISE 3G...
Page 158: ...158 1 1 1 2 2 1 2 2 2 3 2 4 2 5 WILO SE 04 2020...
Page 159: ...159 Wilo Multivert MVISE 3G 2 6 2 7 2 8 4 3 30 C 60 C 4 4 1...
Page 163: ...163 Wilo Multivert MVISE 3G 5 2 6 2 2 10 7 7 1 7 2 Fig 1 10...
Page 164: ...164 7 3 M10 20 M12 30 7 4 5 3 kW 1 1 2 M25 Ext Off Aux kW 1 1 2 WILO SE 04 2020...
Page 165: ...165 Wilo Multivert MVISE 3G gF RCD 30 25 A B 2...
Page 176: ...176 Fig A2 EASY EXPERT EXPERT Fig A4 Information EASY Fig A3 WILO SE 04 2020...
Page 180: ...180 Fig A5 Information SSM SBM Ext Off INFORMATION 4000 WILO SE 04 2020...
Page 181: ...181 Wilo Multivert MVISE 3G 9 2 ON 7 0 0 0 2 OFF A1 1...
Page 182: ...Wilo 182 10 20 30 Wilo Wilo WILO SE 04 2020...
Page 183: ...183 Wilo Multivert MVISE 3G 9 2 SBM 5 7 6 0 3 1 2 3 SSM 1 6 6 24 SBM 24 SBM SSM 1 2 3 4 5 6 24...
Page 185: ...185 Wilo Multivert MVISE 3G 10 2 6 0 0 0 24 1 6 300...
Page 186: ...186 11 Wilo www wilo com 12 www wilo recycling com WILO SE 04 2020...
Page 187: ...187 Wilo Multivert MVISE 3G...
Page 217: ...217 Kurulum ve al t rma talimatlar Wilo Multivert MVISE 3G...
Page 218: ...218 1 1 1 2 2 1 2 2 2 3 2 4 IEC VDE WILO SE 04 2020...
Page 219: ...219 2 5 IEC VDE 2 6 2 7 2 8 4 3 30 C 60 C 4 Wilo Multivert MVISE 3G...
Page 223: ...223 7 7 1 7 2 Fig 2 10 Wilo Multivert MVISE 3G...
Page 224: ...224 7 3 M10 20 M12 30 7 4 5 1 1 2 M25 WILO SE 04 2020...
Page 225: ...225 2 Ext Off Aux gF FI 30 25 B 1 1 2 M20 M12 M25 M12 M16 Wilo Multivert MVISE 3G...
Page 236: ...Fig A2 EASY EXPERT EXPERT Fig A4 EASY Fig A3 236 WILO SE 03 2019 WILO SE 04 2020...
Page 240: ...240 Fig A5 Information SSM SBM Ext Off INFORMATION 4000 WILO SE 04 2020...
Page 241: ...241 DIP 2 ON 7 0 0 0 DIP 2 OFF 9 Wilo Multivert MVISE 3G...
Page 242: ...242 10 Wilo 20 30 Wilo Wilo WILO SE 04 2020...
Page 245: ...245 10 2 6 0 0 0 24 1 6 300 Wilo Multivert MVISE 3G...
Page 246: ...246 11 Wilo 12 www wilo recycling com WILO SE 04 2020...
Page 254: ......
Page 255: ......
Page 256: ......