Page 28 | 1-800-343-9463
PS
011717
Platinum Split Wiring 115V with Cold Weather Start Kit
Inside AKA4457 Electrical Boxes
Compressor Contactor (Magnecraft Relay) VWC P/N 1-141120
Purpose- Cycle power between the crank case heater and
compressor, as needed. Crank case heater will be turned off, and
compressor will be turned on when the 24V coil relay is energized
giving power to the bypass timer activating its 1000 seconds timer.
Compressor will be turned on, and crank case heater will be turned
off when the low pressure switch is closed. Compressor will be
turned off and Crank case heater will turned on when low pressure
switch is opened.
Lever Connector labeled
F
VWC P/N
1-422128
Purpose- to house the fan hot
wire and one fan cycling switch wire.
Lever Connector labeled
H
VWC P/N 1-422128
Purpose- to house the hot
wire from the power cord, wire (A) that connects to the # 8 terminal on the
Magnecraft relay, one low pressure switch wire and wire (8) that connects to
lever arm connector (H2),
Lever Connector labeled
N
VWC P/N 1-422128
Purpose- to
house the neutral wires.
Lever Connector labeled
H2
VWC P/N 1-422128
Purpose-
to house wire (8) that connects to lever arm connector (H),
wire (9) that connects to the thermal switch, wire (7) that
connects to the # 6 terminal on the Magnecraft relay in the
other electrical box, and wire (6) that connects to the 24V
coil relay.
Lever Connector labeled
L
VWC P/N 1-422128
Purpose- to house one fan cycling switch wire, wire
(10) that connects to the # 8 terminal on the
Magnecraft relay in the other electrical box, and wire
(B) that connects to the #1 terminal on the Magnecraft
relay.
Wire
E
sends power out from the Magnecraft relay
to the overload (Connected to terminal
#6
on the
Magnecraft relay).
Wire
A
receives power from the lever arm
connector
H
and sends power to the
Magnecraft Relay (Connected to terminal
#8
on the Magnecraft relay).
Crank case heater wire sends power out from the Magnecraft
relay to the crank case heater (Connected to terminal
#7
on the
Magnecraft relay).
Wire
B
sends power out from the
Magnecraft relay to the lever arm
connector labeled
L
(Connected to terminal
#1
on the Magnecraft relay)
Inside AKA4457 Electrical Boxes
Wire
11
connects to a low pressure switch
with a wire nut (Connected to terminal
#1
on the Magnecraft relay)
Lever Connector labeled
N2
VWC P/N 1-422128
Purpose- to
house the neutral wires.
(Magnecraft Relay) VWC P/N 1-141120
Purpose- to
assist in the start of the unit.
Wire
12
connects to a wire nut (Connected to terminal
#0
on the
24V coil relay)
Wire
2
sends power out from bypass timer the to
the Magnecraft relay (Connected to terminal
#7
on
the Magnecraft relay)
Wire
10
sends power out from the Magnecraft relay to
the lever arm connector
L
(Connected to terminal
#8
on the Magnecraft relay)
Wire
7
receives power from the lever arm connector
H2
and sends power to the Magnecraft Relay (Connected to
terminal
#6
on the Magnecraft relay)
Wire
13
connects to a wire nut
(Connected to terminal
#1
on the 24V coil
relay)
Wire
6
receives power from the lever arm connector
H2
and sends power to the 24V coil relay (Connected
to terminal
#4
on the 24V coil relay)
Wire
1
sends power to the bypass timer terminal
#2
(Connected to terminal
#6
on the 24V coil relay)
Wire
4
connects to terminal
#3
on the bypass timer to the lever
arm connecter labeled
N2
Wire
1
receives power from the 24V coil relay
terminal
#6
(Connected to terminal
#2
on the bypass
timer)
Wire
2
sends power from the bypass timer to the
#7
terminal on the Magnecraft relay (Connected to
terminal
#1
on the Bypass Timer)