Platinum Split
INSTALLING THE CONDENSING UNIT
The Condensing Unit can be installed inside a well-ventilated area of the home, but is typically installed outside. Exterior
applications will require the use of a protective housing. The amount of sun exposure should be considered when selecting
the placement of the Condensing Unit .The Condensing Unit requires a dedicated 20-amp circuit (non-GFI). Make sure there is
a minimum of three (3) feet of horizontal clearance in every direction around the unit (five feet is ideal). The unit may either be
hard-wired or plug-in, depending on local electrical codes.
Inside Condensing Unit Installations: Inside installations require special consideration, as there must be adequate
ventilation to remove the heat created during normal operations. An exhaust port with fan may need to be installed to
ensure that heat is effectively removed from the utility room. There must be a return grille or provision for 500 - 600 CFM
of cool air to enter the room to replace the exhausted air. Unobstructed airflow to and from the unit is a critical factor in
the unit’s overall performance. Make sure there is a minimum of three (3) feet of horizontal clearance in every direction
around the unit (five feet is ideal). This will assure that the unit can move the air around the room in an efficient manner.
Outdoor Condensing Unit Installations: You must utilize the exterior Condensing Unit housing for outdoor
installations. Place the Condensing Unit on a solid foundation in a location with adequate ventilation. Make sure there is a
minimum of three (3) feet of horizontal clearance in every direction around the unit (five feet is ideal). The unit should be
elevated 18 inches in order to avoid any possible flooding or damage by animals, and should be clear of leaves, dirt, and
other debris.