1. Overview
1.9 Site Requirements
The E3000 is designed to be installed into a rack that meets the EIA-310 standard with a minimum of 1000
mm (39.4 in.) of usable rack space, frame to frame. The vertical rack rails must be set between 718 mm
(28.26 in.) – 850 mm (33.46 in.) to support the enclosure. It requires 3U of rack space, and it should be
installed into the rack at the lowest possible U height to keep the load on the rack balanced.
Table 20:
Required Rack Specifications
Parameter
Requirement
Rack Depth
1000 mm (39.4 in.) of usable rack space, frame to
frame
Rack Width
450mm (17.72in.) with 465mm (18.31in.) ± 1.5mm
nominal hole spacing. See EIA-310 Rack Standard
Rack Units (U)
3U
Vertical Rack Rail Spacing
718 mm (28.26 in.) – 850 mm (33.46 in.)
Static Load Rating
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet
Dynamic Load Rating
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet
1.9.3
Thermal and Cooling Requirements
The thermal output of the enclosure depends on the number of F3x00s that are populated in the E3000
chassis. Use the following table to determine how many BTUs of heat will exhaust from the rear of the unit.
Table 21:
BTU Exhaust per Component
Condition
Typical BTU Output
Max BTU Output
Single E3000 with BMC Module 768 BTU/hr = 225 W
(25C/77F, fans at 50%)
1177 BTU/hr = 345 W
(35C/95F, fans at 100%)
Single F3x00
409 BTU/hr = 120 W
(25C/77F, Workload: Random
Read/Write, queue depth
32, 80% internal processors
dedicated to workload)
546 BTU/hr = 160 W
(35C/95F, Workload: Highest
throughput to drives – Seq
Write, queue depth 32, all
internal processors at 100%)
E3000 Fully Populated with
F3x00s
5244 BTU/hr = 1537 W
(25C/77F, fans at 50%)
5884 BTU/hr = 1725 W
(35C/95F, fans at 100%)
1.9.4
Installation and Servicing Requirements
18