7 Commissioning
WARNING!
Manipulation of the controller!
During commissioning, the system may be
manipulated to such an extent that this can
result in risks to life and material damage.
▶
Make sure that system components can-
not start up unintentionally!
The procedures applied during commissioning depend on
which fieldbus protocol has been chosen and which control
-
ler is being used.
7.1
Setting the fieldbus protocol
The fieldbus protocol and the module behaviour in the net
-
work are set using the rotary switches. The module adopts
and saves these settings upon the next instance of the pow-
er supply being switched on.
The fieldbus protocol can only be set
(changed) if the module is using the factory
settings.
Any changes made to the position of the
rotary switch only take effect once the power
supply has been switched off and back on
again.
x100
x10
x1
0 E/IP
PN
0
0
2
1
0
Example: Setting the value of „210“ (IP address 192.168.1.210 for Ethernet/IP)
The following table shows the rotary switch settings pos-
sible.
Setting
Protocol
Function
000
Ethernet/IP
The previously saved network settings are used.
When in the delivery condition, the network parame-
ters are requested via DHCP/BOOTP.
001 to 254
Ethernet/IP The last byte of the IP address is overwritten with
the set value (192.168.1.XXX).
255 to 298
Ethernet/IP The network parameters are requested via DHCP/
BOOTP, but are not saved.
299
Ethernet/IP The factory settings for the IP address are used
(192.168.1.1).
300 to 399
PROFINET Network parameters are allocated via DCP.
900 to 999
(Exception: 979)
–
Invalid setting
979
–
Restoring factory settings
Only use DHCP/BOOTP if a suitable server is
in the network which can assign the network
parameters to the module.
▶
Restore the factory settings using the rotary switch
(see section 7.2).
▶
Turn the left rotary switch (“x100”) to a value from 0 to 3.
▶
Turn the middle rotary switch (“x10”) to a value from 0 to
9.
▶
Turn the right rotary switch (“x1”) to a value from 0 to 9.
▶
Switch the power supply off and back on again
The modules adopts the news settings.
If an invalid setting has been made, the BF/MS LED will flash
red three times.
7.2 Restoring factory settings using the rotary
switch
The module‘s factory settings can be restored via the rotary
switch. The protocol settings can be reset in the same way.
The
Factory settings
web server function
does not reset the protocol settings.
▶
Turn the left rotary switch (“x100”) to the value 9.
▶
Turn the middle rotary switch (“x10”) to the value 7.
▶
Turn the right rotary switch (“x1”) to the value 9.
▶
Switch the power supply off and back on again
The module is reset to factory settings.
7 Commissioning
| Setting the fieldbus protocol
23
2484940000/00/02.2017
Manual UR67-Multiprotocol