7 Commissioning
| Commissioning with PROFINET
31
2484940000/00/02.2017
Manual UR67-Multiprotocol
▶
Change the device names as required.
▶
Check whether the displayed IP address is correct and
whether the controller and module are in the same Ether-
net subnet.
▶
Confirm the settings by clicking
OK
.
All settings only take effect once they have been
loaded into the module/control unit (see below).
Assigning a device name to a UR67-MP module
To assign a device name to a module, the PC must be con-
nected to the module via a PROFINET connection.
▶
Select the module.
▶
Open the dialogue box
PLC
/
Ethernet
/
Assign device
name
.
Assigning a device name
▶
Select the UR67-MP module required.
▶
Click
Assign name
.
▶
Close the dialogue box.
Device replacement without interchangeable medium/PG
The UR67-MP modules support the “Device replacement
without interchangeable medium/PG” function. Modules in a
PROFINET network can be exchanged for identical modules
without having to reassign the device name using a program-
ming device.
The IO controller (e.g. a controller) assigns the module
exchanged-in the device name based on the configured to
-
pology and the real neighbourhood relationship determined
by the IO devices. In order to use the “Device replacement
without interchangeable medium/PG”, the following require-
ments must therefore be fulfilled:
–
The IO controller must support the “Device replacement
without interchangeable medium/PG” function.
–
The neighbouring PROFINET devices of the module to be
exchanged must support the “Device replacement with-
out interchangeable medium/PG” function.
–
The function must be activated for the IO controller.
–
The PROFINET network topology must be configured and
match the real topology.
–
The device to be exchanged-in must be set to its factory
settings.
If the user intends to use the “device replacement
without interchangeable medium/PG” function,
the device to be exchanged-in must be reset to its
factory settings before being swapped in.
“Device replacement without interchangeable medium/PG”
can be configured in STEP 7.
▶
In the hardware configuration tool, double-click the
PROFINET IO port (
PN-IO
) for the controller in order to
open the
PN-IO properties...
window.
▶
Activate
Support device exchange without
exchangeable medium
and close the window by click-
ing
OK
The PROFINET network topology must be configured. Plan
the connection of the PROFINET port for the individual de-
vices.
▶
In the hardware configuration tool, click on the PROFINET
port of a device for which you want to configure its con-
nection.
▶
Switch to the
Topology
tab.
▶
In the
Partner Port
menu, select the port for the neigh-
bouring device and confirm by clicking
OK
.
▶
Repeat this process until all of the connections have been
configured.
Alternatively, the topology can be configured using the
SIMATIC Topology Editor.