4 Module descriptions
| Technical Data
12
2484940000/00/02.2017
Manual UR67-Multiprotocol
4.5 Technical Data
Technical data
UR67-MP-xx-16DI-12-60M
(2426270000, 242630000)
UR67-MP-xx-16DO-12-60M
(2426280000, 2426310000)
UR67-MP-xx-8DIDO-12-60M
(2426290000, 2426320000)
Bus system
Protocol
Ethernet/IP, PROFINET
Vendor name (for Ethernet/IP)
1015
Product type, number (for Ethernet/IP)
7
Product type, string (for Ethernet/IP)
General Purpose Discrete I/O
Product code (for Ethernet/IP)
34003 (for UR67-MP-HP-16DI-12-60M)
34000 (for UR67-MP-78-16DI-12-60M)
34004 (for UR67-MP-HP-16DO-12-60M)
34001 (for UR67-MP-78-16DO-12-60M)
34005 (for UR67-MP-HP-8DIDO-12-60M)
34002 (for UR67-MP-78-8DIDO-12-60M)
VendorID (for PROFINET)
0x0134 hex
DeviceID (for PROFINET)
0x18C6 hex
EDS file (for Ethernet/IP)
WM_xx_Vz.z-WI-UR67-yyyymmdd.eds
GSDML file (for PROFINET)
GSDML-Vx.x-WI-UR67-yyyymmdd.xml
Data transmission rate
10/100 Mbps, Full Duplex (Ethernet/IP)
100 Mbps, Full Duplex (PROFINET)
Transmission method
100BASE-TX
Auto-negotiation
Supported
Switch functionality
Integrated, 2 connections
IRT supported (PROFINET)
Ethernet protocols supported
Ping, ARP, DHCP, HTTP, TCP/ IP, BOOTP, beacon-based DLR (Ethernet/IP)
Ping, ARP, LLDP, DCP, HTTP, TCP/ IP, SNMP (PROFINET)
Connection
M12, 4-pole, D-coded
Inputs
Number of digital channels
16
–
8
Channel type
NO contact, P-switching
–
NO contact, P-switching
Input wiring
Type 3 in acc. with IEC 61131-2
–
Type 3 in acc. with IEC 61131-2
Rated input voltage
24 V DC
–
24 V DC
Input current at 24 V DC
typically 5 mA
–
typically 5 mA
Short-circuit-proof
Yes
–
Yes
Status indicator
Yellow LED (channel A)
White LED (channel B)
–
Yellow LED (channel A)
White LED (channel B)
Diagnosis indicator
Red LED for every M12 socket
–
Red LED for every M12 socket
Connection
M12, 5-pole, A-coded
–
M12, 5-pole, A-coded
Outputs
Number of digital channels
–
16
8
Channel type
–
NO contact, P-switching
NO contact, P-switching
Output wiring
–
typically 1.6 A in acc. with IEC 61131-2
typically 1.6 A in acc. with IEC 61131-2
Rated output current per channel
1)
–
1.6 A
1.6 A
Signal status “1”
–
max. 1.6 A
max. 1.6 A
Signal status “0”
–
max. 1 mA (specification as per standard) max. 1 mA (specification as per standard)
1) In the case of inductive loads in utilisation category DC13 (in acc. with EN 60947-5-1), the outputs can operate with currents of 0.5 A and a frequency of 1 Hz.
2) Technically possible and approved on the following conditions: looped system/sensor power supply – max. 2.5 A; minimum cross-section of power supply wire –
5 x 1.0 mm²; max. ambient temperature – 40°C (104°F)