DETAILED PARAMETER DESCRIPTION
Factory
Standard
min.
Range
max.
shortest step
1
1
30
1
P62 -
Address of the Soft-Starter on the
Communication Network
6.4.15 - P63 - Watch Dog
Time of the
Serial
Communication
This parameter can enable or disable the serial
communication watch dog, as well as set the watch dog
time. This protection (E29 Error) acts when the serial
communication between the master and the Soft-Starter
is interrupted, causing the action as set in parameter P64.
NOTE!
Enable this function only if there is
cyclic
serial communica-
tion with a Master.
Set the watch dog time according to the time between
telegrams sent by the Master.
Factory
Standard
min.
Range
max.
shortest step
OFF, 1
1s
5s
OFF
P63 -
Watch Dog Time of the Serial
Communication
6.4.16 - P64 - Action
After Watch Dog
Time is Elapsed
This parameter sets the action to be adopted after the
watch dog time is elapsed.
NOTE!
P63 must be set different from OFF.
Values of P64:
1- Indicates only E29 error on the HMI of
the Soft-Starter.
2 - Indicates E29 error and disables the Soft-
Starter by ramp, if P04 is programmed
different from OFF. If P04=OFF, the
motor is stopped by inertia.
3 - Indicates E29 error and causes general
disabling of the Soft-Starter. Its acts as
Emergency. The motor is stopped by
inertia.