22
INSTALLATION
3
3.1.3 - Kit IP20
The use of the IP20 Kit permits the installation of the input
and output cables, ensuring a degree of protection IP20, and
consequently not permitting direct access to conductive parts,
since it does not have openings larger than 12 mm (0.47 in).
Table for conduits of the Kit IP20
Type
SSW-03 Plus ( A )
120
170
205
255
290
340
410
475
580
670
800
950
Control
Conduit
( In )
½
½
½
½
½
½
½
½
½
½
½
½
Power
Conduit
( In )
1 ½
2 ½
2 ½
3
3
3
3
4
4
5
6
6
Grounding
Conduit
( In )
1
1
1
1 ½
1 ½
1 ½
1 ½
1 ½
1 ½
2
2 ½
2 ½
Kit IP20
Weg Item-N
o
417112100
417112101
417112101
417112102
417112102
417112102
417112103
417112104
417112104
417112105
417112106
417112106
NOTE!
The connection can not be performed within the delta
connection of the motor when Kit IP20 is used.
Table with Kit IP20 Dimensions - See Figure 3.3
Type
SSW-03 Plus ( A )
120
170
205
255
290
340
410
475
580
670
800
950
Width
L
mm (in)
224 (8.82)
224 (8.82)
224 (8.82)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
521 (20.51)
Height
H
mm (in)
365 (14.37)
480 (18.90)
480 (18.90)
530 (20.86)
530 (20.86)
530 (20.86)
605 (23.81)
655 (25.78)
655 (20.86)
705 (27.75)
855 (33.66)
855 (33.66)
Depth
P
mm (in)
244 (9.61)
257 (10.12)
257 (10.12)
315 (12.40)
315 (12.40)
315 (12.40)
325 (12.79)
325 (12.79)
325 (12.79)
325 (12.79)
345 (13.58)
345 (13.58)
Height
H1
mm (in)
240 (9.45)
240 (9.45)
240 (9.45)
356 (14.01)
356 (14.01)
356 (14.01)
356 (14.01)
356 (14.01)
356 (14.01)
406 (15.98)
483 (19.01)
483 (19.01)
Height
H2
mm (in)
605 (23.82)
720 (28.34)
720 (28.34)
886 (34.88)
886 (34.88)
886 (34.88)
961 (37.83)
1011 (39.80)
1011 (39.80)
1111 (43.74)
1288 (50.70)
1288 (50.70)