65
Factory
Standard
Possible Values
P22 -
Rated current of the Soft-Starter
120, 170, 205, 255, 290, 340, 410, 475,
580, 670, 800, 950, 1100, 1400A
According
to the
type
6.3.12 - P23 - Rated
voltage of the
Soft-Starter (V)
The function is to calculate the power supplied to the
load.
6.3.13 - P31 - Phase
rotation
(ON = RST;
OFF = any
sequence)
This function can be enabled or disabled, but when
enabled its function is to protect the loads that can
not be driven in both directions of rotation.
NOTE!
The phase sequence is only detected at the first time when
the power part is activated after the electronic part has
been energized. Thus a new phase sequence can only be
detected when the electronic part is switched OFF or reset.
Factory
Standard
380
Possible Values
P23 -
Rated voltage of the Soft-Starter
220, 230, 240, 380, 400, 415,
440, 460, 480, 525, 575V
6
DETAILED PARAMETER DESCRIPTION
NOTE!
1)
When a Soft-Starter is connected within the motor delta
connection (P28=ON), the rated current of the Soft-
Starter is set automatically to 1.73 x I
N
, of the Soft-Starter.
2)
Do not change this value, since the content of this
parameter is specific for each software.
Factory
Standard
OFF
Possible Values
P31 -
Phase rotation
OFF, ON