DETAILED PARAMETER DESCRIPTION
6.3.10 - P15 -
Immediate
undercurrent
Time(s)
Through this parameter is determined the maximum
time that the load can operate with undercurrent,
as set in P14. Typical application for this function is
in pumping systems that benefit when they are dry
operated.
Factory
Standard
OFF
P15 -
Immediate undercurrent Time
min.
Range
max.
shortest step
OFF, 1s
1s
200s
6.3.11 - P22 - Rated
current of the
Soft-Starter (A)
It is function is to adjust the Software to certain
conditions of the hardware, being used as base of the
following functions: starting current limitation (P11);
immediate overcurrent (P12) at duty; undercurrent at
duty (P14) and thermal overload protection of the motor.
6.3.9 - P13 - Immediate
Overcurrent
Time(s)
This parameter determines the maximum time that the
load can operate with overcurrent, as set in P12.
of the switch = 120A
of the motor = 140A
70% of 140A = 0.7 x 140A = 98A
of the switch within delta
120A x 1.73 = 207.8A
P14 = 47% of
of the switch = 70% of
of the motor
98A
delta switch
0.47 x switch
=
98A
207.8A
=
2) Within the motor delta connection
Factory
Standard
OFF
min.
Range
max.
shortest step
OFF, 1s
1s
20s
P13 -
Immediate Overcurrent Time