90
6
DETAILED PARAMETER DESCRIPTION
NOTE!
Please note that every time you use this function you can
reduce the winding life of your motor.
Figure 6.12
-
Auto-reset of the thermal memory
Factory
Standard
min.
Range
max.
P27 -
Auto-reset of the thermal memory OFF, 1
1s
600s
OFF
shortest step
Motor
On
Off
t
t
t
t
EO4
EO4
Motor
On
Off
actuation
level
without reset
with reset
actuation
level
auto-reset time
6.5.4 - P27 - Auto-reset
of the Thermal
motor image
It sets the time for the auto-reset of the thermal motor
image. The thermal decrement of the thermal motor
image simulates the motor cooling time with load and
without load, ON and OFF. The algorithm that realizes
this simulation is base on tests applied on WEG motors
IP55 standard according to your power programmed
in the Soft-Starter parameters.
In application, where several starts per hour are
required, you can use the auto-reset of the thermal
image.